NA7.20.1.1.1 Construction Inspection

p.6052025 Nonresidential Appendices generally occurs during periods where ambient conditions are above 75F to 80F, where the high pressure CO2 vapor will not condense (or partially condense) in the gas cooler, and pressure and temperature can vary semi-independently during the heat rejection process. Because these two modes of operation are based on ambient conditions, it may not be possible for the field technician to observe both subcritical and supercritical control strategies during a single acceptance test.

p.6062025 Nonresidential Appendices temperature) during subcritical operation, as long as the setpoint value is similarly expressed in pressure or temperature.

p.6063. Documentation may be achieved through pictures of control system screens or control system documentation, supported by sample calculations of observed pressures or temperatures and associated conversion values, as available in the control system interface.

p.605The field technician shall perform either the functional test outlined in NA7.20.1.1.2 or NA7.20.1.1.3 depending on the ambient conditions and resulting system operating mode at the time of the test. The construction inspection must be completed regardless of ambient conditions.

p.606(c) Verify the gas cooler outlet temperature sensor reads accurately, using a NIST

p.606traceable instrument, including verification of at least two different gas cooler outlet readings. Calibrate if needed. Replace if outside manufacturer’s recommended calibration range. If multiple gas coolers are installed in parallel, ensure sensor is installed on the common header.

p.605The following test methods are general in nature, with the understanding that refrigeration systems are commonly custom designed, with many design choices, as well as varying load profiles. For all of these reasons, a thorough understanding of both refrigeration system design and refrigeration control system operation is necessary to effectively conduct these tests.

p.606(d) Verify the discharge pressure sensor (or gas cooler pressure if used) reads

p.606accurately, using a NIST traceable reference pressure gauge or meter, and with pressure checked for at least two pressures within the typical operating range. Calibrate if needed. Replace if outside manufacturers recommended calibration range.

p.605The measurement devices used to verify the refrigeration system controls shall be calibrated to a NIST traceable reference, with a calibration reference dated within the past two years. The calibrated measurement devices to be used in these acceptance tests are called the "standard" and shall have the following measurement tolerances: The temperature measurement devices shall be calibrated to +/- 0.7°F between -30°F and 200°F. The pressure measurement devices shall be calibrated to +/- 7.5 psi between 0 and 1500 psig.

p.606(e) Verify the ambient dry bulb temperature using a NIST traceable instrument,

p.606including verification of at least two different ambient readings. Calibrate if needed. Replace if outside manufacturer’s recommended calibration range. If the ambient dry bulb temperature sensor is installed between the adiabatic pad and the gas cooler coil for adiabatic gas coolers, verification must be performed when operating in “dry” mode.

p.605NA7.20.1.1 Air-Cooled and Adiabatic Gas Coolers and Gas Cooler Fan Motor Variable Speed Control Conduct and document the following functional tests on all air-cooled and adiabatic gas coolers.

p.606(f) Verify the ambient dry bulb temperature is not mounted in direct sunlight or is

p.606provided with a suitable solar shield.

p.606(g) Verify that all sensor readings used by the gas cooler controller display correct

p.605NA7.20.1.1.1 Construction Inspection Prior to functional testing, verify and document the following:

p.606values at the controller, as well as derived values (e.g., observed pressure is correctly converted saturation temperature for CO2).

p.605(a) Verify the control system minimum saturated condensing temperature (SCT)

p.606(h) Verify that all fan motors are operational and rotating in the correct direction.

p.605setpoint is at or below 60°F. If the design saturated suction temperature (SST) of the intermediate suction group is greater than or equal to 30°F, verify the control system SCT setpoint is at or below 70°F.

p.606(i) Verify that gas cooler fan speed controls are operational and controlling all gas

p.606cooler fan motors in unison.

p.606(j) Verify that all speed controls operate automatically in response to changes in

p.605(b) Verify accuracy of refrigerant pressure-temperature conversions and consistent

p.606pressure, gas cooler outlet temperature, and ambient dry bulb or precool air temperature.

p.605use of either temperature or pressure for the controlled variable setpoint in the control system.

p.606(k) Verify the installation of the gas cooler holdback valve, which may be located

p.6051. The condensing temperature has an equivalent pressure during subcritical operation.

p.606near the inlet of the intermediate pressure vessel or near the outlet of the gas cooler.

p.6052. Either pressure or temperature may be used in the control system as the controlled variable to maintain gas cooler pressure (condensing

p.605Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processesp.606

p.606Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes