RA3.4.4.2 Rated Heat Pump Capacity Verification Procedure

p.3712025 Residential Appendices RA3.4.4.2 Rated Heat Pump Capacity Verification Procedure

p.3722025 Residential Appendices Compliance with Section 150.0(m)13 is not required for systems that use this VCHP performance compliance option. However there are requirements for verification of minimum airflow rates for VCHP system indoor units that are specified as eligibility requirements for this compliance option.

p.3732025 Residential Appendices If the system does not meet the RA3.1.4.3.8 requirements, then the system does not comply with the VCHP compliance option eligibility requirements.

p.3742025 Residential Appendices For indoor units of single-split systems, the measured value for airflow in cfm shall be converted into cfm per ton by dividing the measured indoor unit airflow rate by the nominal tons of outdoor unit cooling capacity.

p.371When heat pump systems are installed, and verification of the installed heat pump system capacity is required, the installed heat pump equipment shall be verified according to the procedure specified in this section. The verification shall utilize certified rating data from the AHRI Directory of Certified Product Performance at http://www.ahridirectory.org or another directory of certified product performance ratings approved by the Energy Commission for determining compliance (product directory).

p.373(e) Ductless space conditioning system indoor units located entirely in conditioned space

p.372(a) Low-static system certification for ducted systems. The manufacturer of ducted indoor

p.373verification. Ductless systems shall be verified in accordance with the ductless space conditioning system indoor units located entirely in conditioned space procedure in RA3.1.4.1.8 to visually confirm ductless indoor units are located entirely in conditioned space.

p.374For indoor units of multiple-split systems, the measured value for airflow in cfm shall be converted into cfm per ton by dividing the measured indoor unit airflow rate by the nominal tons of indoor unit cooling capacity.

p.372units shall certify to the Energy Commission that the system is a VCHP that meets the definition of a low-static system as defined in 10 CFR Parts 429 and 430, Docket No. EERE– 2016–BT–TP–0029, Federal Register Vol. 82, No. 3, January 5, 2017). The manufacturer's model number(s) shall be included in listings of certified-to-the-Energy Commission low- static pressure VCHP systems which will be published on the Energy Commission's website.

p.374If the indoor unit does not meet or exceed the 350 cfm/ton minimum airflow rate required for new systems, or the 300 cfm/ton required for altered systems meeting the refrigerant charge minimum airflow rate, then the system does not comply with the VCHP compliance option eligibility requirements.

p.371The procedure shall consist of visual verification of the model numbers of the installed system equipment and confirmation that the installed equipment is rated to provide the required heating capacity:

p.373If the system is not considered to be entirely in conditioned space according to RA3.1.4.1.8 requirements, then the system does not comply with the VCHP compliance option eligibility requirements.

p.372If the installed VCHP system has ducted indoor units, then verification of the Energy Commission listings of certified VCHP systems shall confirm the installed system is included in the Energy Commission listings of certified low static systems.

p.371(a) Record the manufacturer name and the model number of the outdoor unit or package

p.373(f) Space-Conditioning System Airflow Supply to All Habitable Spaces. Field verification

p.374(j) Air filter sizing. Ducted low-static VCHP indoor units with any length of duct shall have the

p.371unit.

p.373according to the procedure in RA3.1.4.1.7 shall confirm that airflow is supplied to all habitable spaces in a dwelling that specifies use of the VCHP compliance option.

p.374air filters for the return air inlets verified to confirm the air filter sizing conforms to the procedures in i or ii below as applicable.

p.371(b) Record the manufacturer name and the model number of the inside coil if applicable.

p.372If the VCHP model is not included in the Energy Commission listings of certified low static systems, then the system does not comply with the VCHP compliance option eligibility requirements.

p.373If space conditioning system airflow is not supplied to all habitable spaces in the dwelling as determined by the procedure in RA3.1.4.1.7, then the system does not comply with the VCHP compliance option eligibility requirements.

p.374i. Nominal 2-inch or greater depth air filters shall be sized by the system designer to

p.371(c) Record the name of the product directory used to certify the system performance.

p.374accommodate a maximum allowable clean-filter pressure drop of 0.1 inch wc at the air filter's design airflow rate. Field verification of the system designers sizing methodology shall not be required for nominal 2-inch or greater depth air filters, however verification that the installed 2-inch or greater depth air filter is rated to meet a clean filter pressure drop of less than or equal to 0.1 inch wc at the air filter's design airflow rate shall conform to the procedures in RA3.1.4.8.

p.371(d) Record the certification number of the installed system if certification numbers for listed

p.371products are published by the product directory.

p.372(b) Non-continuous default fan operation certification for ducted systems. The

p.373(g) Wall mounted thermostat in zones > 150 ft2. Field verification according to the procedure

p.372manufacturer may elect to certify to the Energy Commission that their ducted indoor unit + outdoor unit combination does not operate the indoor unit fan continuously by default. This certification is required in order to receive credit for the non-continuous fan operation component of the VCHP compliance option credit.

p.371(e) Record the system's rated heating capacity at 47 degrees F published by the product

p.373in RA3.4.5 shall confirm that VCHP space conditioning zones in the dwelling that are greater than 150 ft2 are controlled by a permanently installed wall-mounted thermostat.

p.371directory.

p.371(f) Record the system's rated heating capacity at 17 degrees F if the value is published by the

p.373If a zone area served by an indoor unit is greater than 150 ft2, and the indoor unit is not controlled by a permanently installed wall-mounted thermostat located in the zone served by the indoor unit as determined according to the procedure in RA3.4.5, then the system does not comply with the VCHP compliance option eligibility requirements.

p.374If any of the indoor unit's applicable nominal 2-inch or greater depth air filters fails to meet the maximum 0.1 inch wc. clean filter pressure drop requirement as verified according to the procedure in RA3.1.4.8, then the system does not comply with the VCHP compliance option eligibility requirements.

p.371product directory.

p.372If the installed VCHP system has ducted indoor units, and the certificate of compliance indicates credit has been taken for non-continuous default fan operation, then visual inspection of the Energy Commission listings of certified VCHP systems shall confirm the installed system is included in the Energy Commission listings and the certification indicates the system is a type with indoor units that does not run the fan continuously during periods when there is no call for conditioning.

p.371If the installed system rated heating capacities at 47 degrees F and 17 degrees F are equal to or greater than the values specified on the Certificate of Compliance, the system complies. If the product directory does not publish capacity ratings at 17 degrees F, then compliance with capacity at 17 degrees F is not required.

p.373(h) Non-continuous fan operation - field verification. If non-continuous indoor unit fan

p.374ii. Nominal one-inch minimum depth air filters shall be allowed if the filter face area is

p.373operation is specified for improved compliance credit for ducted VCHP systems in the CBECC-Res model, and thus the certificate of compliance indicates field verification of non-continuous indoor unit fan operation is required, then the system shall be field verified in accordance with the procedures in RA3.4.6 to confirm that the installed system's indoor unit + outdoor unit combination does not operate the fan continuously when the system thermostat is not calling for conditioning.

p.374sized based on a maximum face velocity of 150 ft. per minute at the air filter design airflow rate according to the procedures in RA3.1.4.7.

p.371RA3.4.4.3 Variable Capacity Heat Pump Performance Compliance Option Eligibility Verification

p.372If the model is not included in the Energy Commission listings of certified low static systems as a type with indoor units that does not run the fan continuously during periods when there is no call for conditioning, then the system does not comply with the VCHP compliance option eligibility requirements.

p.374All of the indoor unit air filters that are required to be sized and verified according to a face velocity specification shall comply with this subsection ii. If any of the indoor unit's applicable nominal 1-inch depth air filters has a face area less than the required face area determined according to the procedures in RA3.1.4.7, then the system does not comply with the VCHP compliance option eligibility requirements.

p.371When a performance certificate of compliance indicates a space conditioning system requires verification of the variable capacity heat pump (VCHP) compliance option eligibility requirements, the installed VCHP system shall be field verified to confirm compliance with the eligibility requirements as specified in this subsection RA3.4.4.3.

p.373If field verification according to RA3.4.6 determines the installed system's indoor unit + outdoor unit combination operates the fan continuously when the system thermostat is not calling for conditioning, then the system does not comply with the VCHP compliance option eligibility requirements.

p.372A revised certificate of compliance may be submitted to the enforcement agency that does not specify credit for non-continuous default fan operation.

p.371If field verification determines the VCHP does not comply with all eligibility requirements in this section, then the dwelling in which the VCHP is installed shall not be eligible to claim the VCHP performance compliance credit for that space conditioning system.

p.374(k) Air filter maximum pressure drop. Ducted low-static VCHP indoor units with any length of

p.372(c) Refrigerant charge verification. The installed system shall have refrigerant charge verified

p.374duct shall have the air filters for the return air inlets verified according to the procedures in RA3.1.4.8 to confirm the air filter is rated to provide a clean filter pressure drop less than or equal to 0.1 inch wc., at an airflow rate greater than or equal to the air filter's design airflow rate.

p.372in accordance with applicable procedures in RA3.2, as specified in Standards Sections 150.1(c)7A and 150.2(b)1Fii, or 150.2(b)1Fiii.

p.373A revised certificate of compliance may be submitted to the enforcement agency that does not specify credit for non-continuous default fan operation.

p.371Compliance with Section 150.0(m)11 (Duct System Sealing and Leakage Testing) is not required for systems that use this VCHP performance compliance option. However, there are requirements to verify that VCHP system indoor unit ducts are located entirely in conditioned space that are specified as eligibility requirements for this compliance option.

p.372If the system does not meet the refrigerant charge verification requirements, then the system does not comply with the VCHP compliance option eligibility requirements.

p.373(i) Minimum airflow rate verification. Each new ducted indoor unit shall have airflow

p.374If verification of the indoor unit's air filters according to the procedures in RA3.1.4.8 determines that one or more of the air filters does not provide clean filter pressure drop less than or equal to 0.1 inch wc., at an airflow rate greater than or equal to the air filter's

p.373verified in accordance with the procedures in RA3.3 to confirm the airflow at full capacity in cooling mode is equal to or greater than 350 cfm/ton of nominal cooling capacity. 300 cfm/ton shall be verified for altered systems if required for compliance with the refrigerant charge verification procedure.

p.372(d) Low leakage ducts located entirely in conditioned space verification. Ducted indoor units

p.372shall be verified in accordance with the Verified Low Leakage Ducts in Conditioned Space procedure in Section RA3.1.4.3.8.

p.371Appendix RA3– Residential Field Verification and Diagnostic Test Protocolsp.372

p.372– Residential Field Verification and Diagnostic Test Protocolsp.373

p.373Appendix RA3– Residential Field Verification and Diagnostic Test Protocolsp.374

p.374– Residential Field Verification and Diagnostic Test Protocols