p.3752025 Residential Appendices design airflow rate, then the system does not comply with the VCHP compliance option eligibility requirements.
p.375RA3.4.5 Verification of Wall-Mounted Thermostat
p.375When compliance requires verification that a wall-mounted thermostat has been installed to control a space conditioning system's indoor unit operation, the system's indoor unit thermostat(s) shall be verified according to the following procedures. If a system has more than one indoor unit, then all of the system's indoor unit thermostats shall be verified according to this procedure.
p.375(a) If the conditioned floor area (ft2) of the zone served by an indoor unit is not a criterion for
p.375determining the compliance requirement for wall-mounted thermostats, then skip to subsection (b) below.
p.375Otherwise, if the conditioned floor area (ft2) of the zone served by an indoor unit is a criterion for determining the compliance requirements for wall-mounted thermostats in the zone, then record the value in square feet for conditioned floor area served by the indoor unit.
p.375i. If the zone area size (ft2) criterion indicates that a wall-mounted thermostat is not
p.375required for the zone, then the indoor unit complies, and no further thermostat verification is required for the zone served by the indoor unit.
p.375ii. If the zone area size (ft2) criterion indicates that a wall-mounted thermostat is
p.375required for the zone, then perform the remaining steps (b) and (c).
p.375(b) If possible, locate the wall-mounted thermostat that controls the indoor unit, and verify
p.375whether or not the thermostat controls the indoor unit by setting the thermostat to a cooling setpoint that is less than the room temperature, or alternatively by setting the thermostat to a heating setpoint that is greater than the room temperature.
p.375If there is no wall-mounted thermostat installed in the zone that controls the indoor unit, then the indoor unit does not comply.
p.375If there is a wall-mounted thermostat installed that controls the indoor unit, but it is not located within the zone served by the indoor unit, then the indoor unit does not comply.
p.375(c) For a wall-mounted thermostat installed in the zone that controls the indoor unit located
p.375in step (b), by visual inspection determine if the thermostat is mounted permanently to the wall. Wall-mounted brackets or other means that facilitate non-permanent attachment of handheld thermostats to the wall do not meet this requirement.
p.375If the thermostat is not permanently mounted to the wall, then the indoor unit does not comply.
p.375RA3.4.6 Verification of Non-Continuous Indoor Unit Fan Operation
p.375When compliance requires field verification that an installed space conditioning system indoor unit does not operate the air distribution fan during periods when the space does not require heating or cooling, the system's indoor unit operation shall be field verified according to the
p.375Appendix RA3– Residential Field Verification and Diagnostic Test Protocols