NA7.5.17.1 Construction Inspection

p.5542025 Nonresidential Appendices (f) Actual condenser water supply temperature increases to meet the new setpoint

p.554within ±2oF.

p.554(g) Cooling tower fan(s) stage properly and/or adjust speed accordingly to meet the

p.554lower setpoint.

p.554(h) Chiller load amperage increase.

p.554Step 3: Restore reset control parameter to automatic control. Verify and document the

p.554following:

p.554(i) Condenser water supply temperature controls modulate as intended.

p.554(j) Actual condenser water supply temperature changes to meet the new setpoint.

p.554(k) Cooling tower fan(s) and chiller(s) stage properly and/or adjust speed accordingly

p.554to return to normal operation and meet the setpoint.

p.554NA7.5.17 Occupied Standby

p.554NA7.5.17.1 Construction Inspection

p.554Prior to Functional Testing, verify and document the following:

p.554(a) Confirm that all spaces served by the zone are eligible to be in occupied standby

p.554mode as specified in Section §120.2(e)3.

p.554(b) Verify that the occupant sensor is placed so that it can detect occupants in the

p.554space without obstruction. Repeat for all spaces served by the zone.

p.554(c) Confirm that the mechanical system is controlled by an independent signal if the

p.554occupant sensor also controls the lighting.

p.554NA7.5.17.2 Functional Testing

p.554Step 1: Put the zone in occupied mode (i.e., adjust the occupancy schedule).

p.554Step 2: Physically occupy the space and confirm that the occupant sensor detects

p.554the presence of an occupant in the zone.

p.554Step 3: Adjust the thermostatic control so that the space temperature is within the

p.554deadband.

p.554Step 4: Confirm that the zone is supplied with minimum ventilation.

p.554Step 5: Adjust setpoint outside of occupied heating/cooling deadband but inside

p.554the occupied standby deadband. Confirm the zone is in heating or cooling mode.

p.554Step 6: Physically vacate all spaces served by the zone.

p.554Step 7: For space conditioning systems that also provide ventilation to the zone,

p.554confirm that within 5 minutes of occupant sensing controls indicating that the zone is unoccupied the setpoint is setup or setback and the zone is within the occupied standby deadband. Occupant sensing controls may have a time delay of up to 20 minutes before indicating the space is unoccupied and occupant sensing zone controls may allow up to an

p.554Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes