p.551NA7.5.15 Supply Air Temperature Reset Controls
p.551The following acceptance tests apply to supply air temperature reset controls.
p.551NA7.5.15.1 Construction Inspection
p.551Prior to functional testing, verify and document the following:
p.551(a) Supply air temperature reset controls are installed as specified by the
p.551requirements of the Section 140.4(f).
p.551Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processesp.552
p.5522025 Nonresidential Appendices (b) All system air temperature sensors are factory or field calibrated within 2% of a
p.552calibrated reference temperature sensor. Attach a copy of the calibration certificate or field verification results.
p.552(c) Document current supply air temperature.