NA7.5.15 Supply Air Temperature Reset Controls

p.551NA7.5.15 Supply Air Temperature Reset Controls

p.551The following acceptance tests apply to supply air temperature reset controls.

p.551NA7.5.15.1 Construction Inspection

p.551Prior to functional testing, verify and document the following:

p.551(a) Supply air temperature reset controls are installed as specified by the

p.551requirements of the Section 140.4(f).

p.551Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processesp.552

p.5522025 Nonresidential Appendices (b) All system air temperature sensors are factory or field calibrated within 2% of a

p.552calibrated reference temperature sensor. Attach a copy of the calibration certificate or field verification results.

p.552(c) Document current supply air temperature.