p.5492025 Nonresidential Appendices (g) The DES/DXAC runs in direct cooling mode.
p.549NA7.5.13.3 Calibrating Controls
p.549Set the proper time and date, as specified by manufacturer’s installation manual for approved installers.
p.549NA7.5.14 Thermal Energy Storage (TES) Systems
p.549The following acceptance tests apply to thermal energy storage systems that are used in conjunction with chilled water air conditioning systems.
p.549NA7.5.14.1 Eligibility Criteria
p.549The following types of TES systems are eligible for compliance credit:
p.549(a) Chilled Water Storage
p.549(b) Ice-on-Coil Internal Melt
p.549(c) Ice-on-Coil External Melt
p.549(d) Ice Harvester
p.549(e) Brine
p.549(f) Ice-Slurry
p.549(g) Eutectic Salt
p.549(h) Clathrate Hydrate Slurry (CHS)
p.549(i) Cryogenic
p.549(j) Encapsulated (e.g., Ice Balls)
p.549The following Certificate of Compliance information for both the chiller and the storage tank shall be provided on the plans to document the key TES System parameters and allow plan check comparison to the inputs used in the compliance software.
p.549Chiller:
p.549(k) Brand and Model
p.549(l) Type (Centrifugal, Reciprocating, Other)
p.549(m)Heat Rejection Type (Air, Water, Other)
p.549(n) Charge Mode Capacity (Tons)
p.549(o) Discharge Mode Capacity (Tons)
p.549(p) Discharge Mode Efficiency (kW/Ton or EER)
p.549(q) Charge Mode Efficiency (kW/Ton or EER)
p.549(r) Fluid Type and Percentage
p.549Storage Tank:
p.549(s) Brand and Model
p.549Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes