p.4212025 Residential Appendices (b) The insulation shall be installed without gaps and voids.
p.421RA3.5.8.2.3 Special Situations--Kneewalls and Skylight Shafts
p.421(a) Framing for kneewalls and skylight shafts that separate conditioned from unconditioned
p.421space shall be insulated to meet or exceed the wall R-value specified on the Certificate of Compliance, and all other required compliance documentation.
p.421(b) Steel-framed kneewalls and skylight shafts, shall exceed the mandatory minimum insulation
p.421requirements and external surfaces of steel studs shall be covered with insulation unless otherwise specified on the Certificate of Compliance using correct U-factors from Joint Appendix JA4, Table 4.3.4 (or U-factors approved by the Commission Executive Director).
p.421(c) The backside of air permeable insulation exposed to the unconditioned attic space shall be
p.421completely covered with a continuous air barrier.
p.421RA3.5.8.2.4 Special Situations--HVAC/Plumbing Closet
p.421Walls of interior closets for HVAC and/or water heating equipment, which require combustion air venting, shall be insulated to at least the same R-value as the other demising walls (i.e., walls separating conditioned space and attached garage), or as specified on the Certificate of Compliance.
p.421RA3.5.8.2.5 Special Situations--Double Walls and Framed Bump-Outs
p.421(a) Insulation shall fill the entire cavity; or an additional air barrier shall be installed inside the
p.421double wall or bump-out and in contact with the insulation so that the insulation fills the cavity formed with the additional air barrier.
p.421(b) Entire double walls and framed bump-outs shall be airtight.
p.421RA3.5.8.2.6 Special Situations--Structural Bracing, Tie-downs, Steel Structural Framing
p.421(a) Framing and bracing used for structural purposes shall be identified on plan documents with
p.421diagrams and/or design drawings.
p.421(b) Insulation shall be installed in a manner that restricts thermal bridging through the structural
p.421framing assembly.
p.421(c) Insulation shall be applied to fully enclose and/or adhere to all sides and ends of structural
p.421assembly framing.
p.421(d) The structural portions of assemblies shall be air-tight.
p.421RA3.5.8.2.7 Special Situations--Window and Door Headers
p.421All window and door headers shall be insulated to a minimum of R-3 between the exterior face of the header and inside surface of the finish wall material.
p.421RA3.5.8.2.8 Special Situation—Gable Ends in Unvented Attics
p.421(a) In unvented attics, where insulation is applied directly to the underside of the roof deck,
p.421framing for gable ends that separate the unvented attic from unconditioned space shall be
p.421Appendix RA3– Residential Field Verification and Diagnostic Test Protocols