RA3.5.8.1.2 R-value Measurement Equipment

p.4202025 Residential Appendices (d) Materials shall be installed according to manufacturer specifications and instructions.

p.420(e) ICF systems are considered an air barrier; however, extension of the air barrier shall be made

p.420across all interconnections of window and door openings, and at all adjoining surfaces of exterior envelope assemblies of different materials (i.e., where ICF walls adjoin framed floors and roof/ceilings).

p.420RA3.5.8.1.2 R-value Measurement Equipment

p.420The ECC-raters shall verify the installed type and thickness of insulation in the ICF system being used for walls, roof/ceilings, and floors, and to ensure that insulation levels and installation integrity meet the R-value specified on the Certificate of Compliance, and all other required compliance documentation.

p.420RA3.5.8.1.3 Certificates

p.420All provisions of Residential Appendix RA2 shall be met. An Insulation Certificate of Installation signed by the installer shall be provided that states the installation is consistent with the Certificate of Compliance, plans and specifications for which the building permit was issued. The ICF installer shall also complete the applicable sections of the Certificate of Installation form and attach a product specification or data sheet for every insulation material used.

p.420RA3.5.8.1.4 Certificates and Availability

p.420All provisions of Residential Appendix RA2 shall be met. The Insulation Certificate of Installation, with insulation material labels or specification/data sheets attached, signed by the ICF installer, shall be available on the building site for each of the ECC-rater's verification inspections. Note: The ECC-rater cannot verify compliance credit without these completed forms.

p.420RA3.5.8.2 Wall Insulation

p.420(a) Connections of ICF walls shall be grouted and sealed meeting manufacturer's specifications.

p.420All plumbing and wiring penetrations through the top and bottom of the ICF, and electrical boxes that penetrate the plane of the ICF shall be sealed. All gaps between interconnecting envelope assemblies of different materials shall have air barrier caulked or sealed with minimally expansive foam or taped.

p.420(b) Bottom connections of ICFs shall be sealed to the ground subfloor or slab, and above ground

p.420subfloor.

p.420(c) Insulation shall uniformly fit across the plane of the wall and taping, caulking, or sealing of all

p.420joints and seams of the ICF shall be maintained to be considered as the air barrier.

p.420RA3.5.8.2.1 Special Situations--Obstructions

p.420(a) Penetrations and obstructions to the ICF shall be completely caulked and sealed.

p.420(b) Insulation shall fill between the sheathing and the rear of electrical boxes and phone boxes.

p.420RA3.5.8.2.2 Special Situations--Rim Joists

p.420(a) All rim-joists shall be insulated to the same R-value as the adjacent walls.

p.420– Residential Field Verification and Diagnostic Test Protocols