RA3.3.3.1.3 System Airflow Rate Measurement Using Powered Flow Capture Hood

p.365The system airflow measurement shall be performed using the following procedures: all registers shall be fully open, and the air filter shall be installed. Turn on the system fan at the cooling speed and measure the airflow at the return grille(s) with a calibrated powered flow hood to determine the total system return airflow. Operation of the powered flow hood shall conform to the specifications in the manufacturer's product documentation. For multiple return systems, the total system return airflow (Qah, cfm) shall be the sum of the airflow measurements at each of the system's return grilles.

p.365RA3.3.3.1.4 System Airflow Rate Measurement Using Traditional Flow Capture Hood

p.365The system airflow measurement shall be performed using the following procedures: all registers shall be fully open, and the air filter shall be installed. Turn on the system fan at the cooling speed and measure the airflow at the return grille(s) with a calibrated traditional flow capture hood to determine the total system return airflow. For multiple return systems, the total system return airflow (Qah, cfm) shall be the sum of the airflow measurements at each of the system's return grilles.

p.365RA3.3.3.1.5 Alternative to Compliance with Minimum System Airflow Requirements for Altered Systems

p.365When an altered space conditioning system is unable to demonstrate compliance with the applicable minimum system airflow rate across the cooling coil required for refrigerant charge verification compliance, the system shall instead comply with Section RA3.3.3.1.5.1 below. If the remedial actions in Section RA3.3.3.1.5.1 fail to bring the system into compliance with the applicable minimum system airflow rate, the installer shall complete the refrigerant charge verification utilizing the highest system airflow rate attainable.

p.365RA3.3.3.1.5.1 Remedial Actions

p.365The installer shall attempt to correct non-compliant system airflow by performing the following remedial actions:

p.365a) Check to determine that the air filter media is clean. If the air filter media is dirty, then

p.365replace it with clean filter media.

p.365b) Open all registers and dampers and remove any obstructions.

p.365c) Replace crushed, blocked, or restricted ducts if possible.

p.365d) Check to determine that the evaporator coil is clean, or that there are no obstructions to

p.365airflow through the evaporator coil. If the evaporator coil is dirty or blocked with debris, if possible, clean the evaporator coil using a method approved by the manufacturer.

p.365e) Set the air handler fan to high speed for cooling and ensure that the blower wheel and

p.365motor are operating properly, within manufacturer’s specifications.

p.365f) Check to determine whether the return duct system or return filter grille is sized too small

p.365for the installed system. If the return duct or return grille is sized too small, if possible,

p.365Appendix RA3– Residential Field Verification and Diagnostic Test Protocolsp.366

p.3662025 Residential Appendices perform applicable alterations work on the return duct system or return grille in order to improve the system airflow rate.

p.366When performing these remedial actions determines that there is a fault, a corrective action shall be performed if possible. In many cases, airflow can be improved by adding a return duct and filter grille or enlarging the existing return duct or filter grille. Alteration of the return duct system is an alternative that shall be considered if applicable to the existing system, and if other remedial actions do not improve the airflow. Alteration of the return duct system to bring the system airflow rate into compliance is expected to be attainable for systems with ducts in an attic space with sufficient clearances for accommodating improvements to the return duct system.