RA3.2.2.6.1 Fixed Metering Device Calculations - Superheat Charging Method

p.3482025 Residential Appendices (h) Operate the air conditioner in cooling mode for 15 minutes to allow the temperatures and

p.348pressures to stabilize before taking any measurements. While the system is stabilizing, proceed with setting up the remaining temperature sensors if used.

p.348(i) If used, place the cotton wick wet-bulb temperature sensor in distilled water, and ensure

p.348it is saturated. Do not get the dry-bulb temperature sensors wet.

p.348(j) If the system has a fixed metering device, at 12 minutes, insert a wet-bulb temperature

p.348sensor into the return plenum at the "Title 24 – Return Plenum Measurement Access" detailed in Section RA3.2.2.3.

p.348(k) If the system has a fixed metering device, after the system has operated for 15 minutes,

p.348and when the return plenum wet-bulb temperature has stabilized, using the temperature sensor already in place, measure and record the return (evaporator entering) air wet-bulb temperature (Treturn, wb).

p.348(l) Using the temperature sensor already in place, measure and record the return

p.348(evaporator entering) air dry-bulb temperature (Treturn, db).

p.348(m)Using the refrigerant gauge or saturation pressure measurement sensor already attached,

p.348measure and record the suction line (low side) pressure, and record the refrigerant saturation temperature corresponding to the measured low side pressure (Tevaporator, sat).

p.348(n) Using the refrigerant gauge or saturation pressure measurement sensor already attached,

p.348measure and record the liquid line (high side) pressure, and record the refrigerant saturation temperature corresponding to the measured high side pressure (Tcondenser, sat).

p.348(o) Using the pipe temperature sensor already in place, measure and record the suction line

p.348temperature (Tsuction,).

p.348(p) Using the pipe temperature sensor already in place, measure and record the liquid line

p.348temperature (Tliquid).

p.348(q) Using the dry-bulb temperature sensor already in place, measure and record the

p.348condenser (entering) air dry-bulb temperature (Tcondenser, db).

p.348The above measurements shall be used to verify the refrigerant charge as described in following sections.

p.348RA3.2.2.6 Refrigerant Charge and Metering Device Calculations

p.348The following steps describe the calculations to determine if the system meets the required refrigerant charge and metering device function using the measurements determined in Section RA3.2.2.5. If a system fails, then remedial actions must be taken by the HVAC system installer. Be sure to run the air conditioner for 15 minutes after the final adjustments before taking any measurements.

p.348RA3.2.2.6.1 Fixed Metering Device Calculations - Superheat Charging Method

p.348The Superheat Charging Method is used only for systems equipped with fixed metering devices. These include capillary tubes and piston-type metering devices.

p.348Appendix RA3– Residential Field Verification and Diagnostic Test Protocols