p.3472025 Residential Appendices (h) If gauge does not read the correct pressure corresponding to the temperature, the gauge
p.347is out of calibration and needs to be recalibrated.
p.347(i) Close the valve to the refrigerant cylinder, and bleed off a small amount of refrigerant to
p.347lower the high side pressure to give a corresponding temperature to between 45°F and 55°F.
p.347(j) Open the valves between the high side gauge and low side gauge.
p.347(k) If the two gauges corresponding refrigerant temperatures do not read within 1°F of each
p.347other, the low side gauge is out of calibration and needs to be recalibrated.
p.347(l) Affix sticker with calibration check date onto refrigerant gauge.
p.347RA3.2.2.4.3 Digital Hygrometer Calibration
p.347Digital hygrometers shall be calibrated according to the manufacturer's recommended procedures. When the manufacturer certifies the calibration for a limited time, the digital hygrometer shall be recalibrated according to the manufacturers required procedure when the calibration period expires.
p.347RA3.2.2.5 Charge Verification Measurements
p.347The following procedure shall be used to obtain measurements necessary to verify the required refrigerant charge.
p.347(a) Follow the manufacturer’s directions and adhere to the manufacturer's limitations on
p.347indoor ambient air temperature (Tindoor air) and outdoor ambient air temperature
p.347(Toutdoor air) applicable to this procedure. Ensure that the return air dry bulb temperature remains equal to or greater than 70°F prior to and while performing the measurements.
p.347(b) Verify that a liquid line filter drier has been installed if required per outdoor condensing
p.347unit manufacturer's instructions and installed with the proper orientation with respect to refrigerant flow, if applicable.
p.347(c) Connect the refrigerant gauges to the service ports, taking normal precautions to not
p.347introduce air into the system.
p.347(d) Attach one pipe temperature sensor to the suction line near the suction line (low side)
p.347service valve and attach one pipe temperature sensor to the liquid line near the liquid line (high side) service valve. The sensors should be positioned to make good contact with the surface of the refrigerant line.
p.347(e) Attach a temperature sensor to measure the condenser entering air dry-bulb
p.347temperature. The sensor shall be placed so that it records the average condenser air entering temperature and is shaded from direct sun.
p.347(f) Insert a dry-bulb temperature sensor into the return plenum at the "Title 24 – Return
p.347Plenum Measurement Access" detailed in Section RA3.2.2.3.
p.347(g) Be sure that all cabinet panels that affect airflow are in place before making
p.347measurements. The temperature sensors shall remain attached to the system until the final charge is determined.
p.347Appendix RA3– Residential Field Verification and Diagnostic Test Protocols