p.3432025 Residential Appendices RA3.2.2.2.1.1 Dry-bulb Air Temperature Measurements
p.343Air temperature measurements made of supply or return airflow and the outdoor air entering the condensing unit shall meet the following specifications:
p.343(a) Accuracy: ± 2°F.
p.343(b) Resolution: 0.2°F.
p.343RA3.2.2.2.1.2 Wet-bulb Air Temperature Measurements Using Wetted Wick
p.343Air temperature measurements made of return airflow using the wetted wick method shall use a temperature sensor and a clean cotton wick wetted with distilled water. Temperature measurements using this method shall meet the following specifications:
p.343(a) Accuracy: ± 2°F.
p.343(b) Resolution: 0.2°F.
p.343RA3.2.2.2.1.3 Wet-bulb air Temperature Measurements Using Digital Hygrometer Device
p.343Air temperature measurements made of return airflow using a digital hygrometer device shall have a probe that is a minimum of 3 inches in length and be capable of measurements for both dry-bulb and wet-bulb temperature. Dry-bulb and wet-bulb temperature measurements made with digital hygrometer devices shall meet the following specifications:
p.343(a) Accuracy: ± 2°F wet-bulb temperature; or a calculated wet-bulb temperature based on
p.343accuracies of ± 3% RH and ± 2.0 degree F Dry bulb temperature.
p.343(b) Resolution: 0.2°F.
p.343RA3.2.2.2.1.4 Refrigerant Lines - Pipe Temperature Measurement
p.343Temperature measurement of suction or liquid refrigerant lines using sensor mounting styles such as pipe-clamp sensors, Velcro strap-on, or an equivalent sensor device or sensor mounting method shall meet the following specifications:
p.343(a) Accuracy: ± 2°F.
p.343(b) Resolution: 0.2°F.
p.343RA3.2.2.2.2 Temperature Sensor Specifications
p.343RA3.2.2.2.2.1 Response Time Qualification Specification for Air Temperature Sensors
p.343Measurements for verification of refrigerant charge require air temperature sensors that pass the following qualifying test:
p.343(a) Using a test enclosure or test environment that is maintained at known dry bulb
p.343temperature T1;
p.343Appendix RA3– Residential Field Verification and Diagnostic Test Protocols