p.399RA3.5.5 RIGID BOARD INSULATION
p.399These procedures detail the installation and inspection protocols necessary to qualify for Quality Insulation Installation (QII) of rigid board insulation sheathing material. These procedures must be field verified before the building construction permit is finalized.
p.399These procedures are to be followed by the insulation installer and an ECC-rater must verify its conformance for meeting the requirements of Sections 150.1(c)1E or 170.2(a)6, and 110.7 of the Standards.
p.399RA3.5.5.1 Thermal Specification
p.399This insulation type is manufactured of different materials and is in sheet or board form. Rigid board insulation materials are typically used on the exterior side of framed wall assemblies and over the top of exterior roof decks. These products also may be used for special situations in rafter spaces of cathedral ceilings, floors, at floor rim joists, and within or on the outside of window and door headers. This insulation type may also be integral to exterior siding materials. Rigid board insulation material most often is used in conjunction with other insulation materials installed within the framed cavity. The R-value is dependent on the type of material and its thickness. Specific product R-values are readily available from the manufacturer for the specific materials being installed. R-value of the product is typically marked on the product. The installed insulation must meet the R-value stated on the compliance documentation.
p.399(a) Requirements for Walls, Ceilings and Floors Materials shall comply with, and be installed in
p.399conformance with, all applicable building codes for building. California Building Code (including, but not limited to, California Electric Code Section 719) and installed to meet all applicable fire codes.
p.399(b) Materials shall meet California Quality Standards for Insulating Material, Title 24, Part 12,
p.399Chapter 4, Article 3, listed in the California Department of Consumer Affairs Consumer Guide and Directory of Certified Insulating Materials.
p.399(c) Materials shall comply with flame spread rating and smoke density requirements of
p.399Chapter 26 and Section 706 of the Title 24, Part 2: all installations with exposed facings
p.399Appendix RA3– Residential Field Verification and Diagnostic Test Protocolsp.400
p.4002025 Residential Appendices must use fire retardant facings which have been tested and certified not to exceed a flame spread index (FSI) of 25 and a smoke development index (SDI) of 450. Insulation facings that do not touch a ceiling, wall, or floor surface, and faced batts on the undersides of roofs with an air space between the ceiling and facing are considered exposed applications.
p.400(d) Materials shall be installed according to manufacturer specifications and instructions.
p.400(e) Rigid board insulation shall be attached according to the manufacturer's specifications.
p.400(f) Rigid board insulation may be used as the air barrier provided it has been tested to
p.400conform to the air barrier performance conditions of the Standards.