RA3.2.3.1 HVAC Installer - Weigh-In Charging Procedure

p.351Split system air conditioners and heat pumps are shipped from the factory charged with a standard amount of refrigerant as indicated on the nameplate. The manufacturer-supplied refrigerant charge is expected to be the correct amount for the system based on a standard liquid line length and diameter. It is the responsibility of the HVAC installer to ensure that the charge is correct for each air conditioner and to adjust the charge based on liquid line dimensions that deviate from the manufacturer's standard line specification.

p.351RA3.2.3.1.1 Procedure Options

p.351There shall be two options for compliance using the weigh-in charging procedure:

p.351RA3.2.3.1.1.1 Weigh-in Charge Adjustment

p.351This option is applicable to a new system or existing system when a new outdoor unit is installed (with factory charge in outdoor unit). The HVAC installer shall weigh in lineset and indoor coil charge adjustment after evacuation of lineset and indoor coil. The documentation shall include the calculated charge adjustment for the lineset.

p.351RA3.2.3.1.1.2 Weigh-in Total Charge

p.351This option is applicable to all systems. The installer shall weigh in the total system charge after refrigerant recovery and evacuation of the entire system. The total system charge includes the nameplate charge for the outdoor unit and any adjustment for the lineset dimensions and indoor coil in accordance with the manufacturer’s instructions. The documentation shall include the nameplate charge and the calculated lineset adjustment.

p.351RA3.2.3.1.2 Minimum Qualifications for this Procedure

p.351Persons who use this procedure to demonstrate compliance with Title 24, Part 6 shall be qualified to perform the following:

p.351(a) Calculate the correct system charge based on the Manufacturer's standard charge and

p.351adjustments to the standard charge based on lineset dimensions and indoor coil.

p.351(b) Obtain accurate refrigerant charge weight.

p.351RA3.2.3.1.3 Instrumentation Specifications

p.351Instrumentation for the procedures described in this section shall conform to the following specifications:

p.351RA3.2.3.1.3.1 Refrigerant Scale

p.351An electronic refrigerant scale having an accuracy equal to or better than ±0.5 oz or ± 0.5% of the measured value shall be used.

p.351RA3.2.3.1.4 Calibration

p.351The accuracy of instrumentation shall be maintained using the following procedures. A sticker with the calibration check date shall be affixed to each instrument calibrated.

p.351Appendix RA3– Residential Field Verification and Diagnostic Test Protocolsp.352

p.3522025 Residential Appendices RA3.2.3.1.4.1 Refrigerant Scale