RA3.2.3.1.4.1 Refrigerant Scale

p.3522025 Residential Appendices Refrigerant Scale

p.3532025 Residential Appendices i. In all cases where the OEM instructions call for checking for gas leaks with vacuum, the system is evacuated to 500 microns or less and, when isolated, rises no more than 300 microns over five minutes.

p.3542025 Residential Appendices

p.3552025 Residential Appendices

p.3562025 Residential Appendices

p.3572025 Residential Appendices

p.3582025 Residential Appendices

Table RA3.2-2Target Superheat (Suction Line Return Temperature Air Wet-Bulb - Evaporator Temperature Saturation (°F) (T return, Temperature) wb)
Condenser (°F) (T Air Dry-Bulb Temperature cond., db)505152535455565758596061626364656667686970717273747576
558.810.111.512.814.215.617.118.520.021.523.124.626.227.829.431.032.433.835.136.437.739.040.241.542.743.945.0
568.69.911.212.614.015.416.818.219.721.222.724.225.727.328.930.531.833.234.635.937.238.539.741.042.243.444.6
578.39.611.012.313.715.116.517.919.420.822.323.825.326.828.329.931.332.634.035.336.738.039.240.541.743.044.2
587.99.310.612.013.414.816.217.619.020.421.923.324.826.327.829.330.732.133.534.836.137.538.740.041.342.543.7
597.58.910.211.613.014.415.817.218.620.021.422.924.325.727.228.730.131.532.934.335.636.938.339.540.842.143.3
607.08.49.811.212.614.015.416.818.219.621.022.423.825.226.628.129.631.032.433.735.136.437.839.140.441.642.9
616.57.99.310.712.113.514.916.317.719.120.521.923.324.726.127.529.030.431.833.234.635.937.338.639.941.242.4
626.07.48.810.211.713.114.515.917.318.720.121.422.824.225.527.028.429.931.332.734.135.436.838.139.440.742.0
635.36.88.39.711.112.614.015.416.818.219.620.922.323.625.026.427.829.330.732.233.634.936.337.739.040.341.6
64-6.17.69.110.612.013.514.916.317.719.020.421.723.124.425.827.328.730.231.633.034.435.837.238.539.941.2
65-5.47.08.510.011.512.914.315.817.118.519.921.222.523.825.226.728.229.731.132.533.935.336.738.139.440.8
66-6.37.89.310.812.313.815.216.618.019.320.722.023.224.626.127.629.130.632.033.434.936.337.639.040.4
67--5.57.18.710.211.713.214.616.017.418.820.121.422.724.125.627.128.630.131.533.034.435.837.238.639.9
68---6.38.09.511.112.614.015.516.818.219.520.822.123.525.026.528.029.531.032.533.935.336.838.139.5
69---5.57.28.810.411.913.414.816.317.619.020.321.522.924.426.027.529.030.532.033.434.936.337.739.1
70----6.48.19.711.212.714.215.717.018.419.720.922.323.925.427.028.530.031.533.034.435.937.338.7
71----5.67.38.910.512.113.615.016.417.819.120.321.723.324.926.428.029.531.032.534.035.436.938.3
72-----6.48.19.811.412.914.415.817.218.519.721.222.824.325.927.429.030.532.033.535.036.537.9
73-----5.67.39.010.712.213.715.216.617.919.220.622.223.825.426.928.530.031.533.134.636.037.5
74------6.58.29.911.513.114.515.917.318.620.021.623.224.826.428.029.531.132.634.135.637.1
75------5.67.49.210.812.413.915.316.718.019.421.122.724.325.927.529.130.632.233.735.236.7
76-------6.68.410.111.713.214.716.117.418.920.522.123.825.427.028.630.131.733.334.836.3
77-------5.77.59.311.012.514.015.416.818.320.021.623.224.926.528.129.731.332.834.436.0
78--------6.78.510.211.813.414.816.217.719.421.122.724.426.027.629.230.832.434.035.6
Table RA3.2-2Target Superheat Return Air (Suction Wet-Bulb LineTemperature Temperature - (°F) (T Evaporator return, wb) SaturationTemperature)
Condenser Dry-Bulb Temperature (T cond., Air (°F) db)505152535455565758596061626364656667686970717273747576
90-------------6.88.810.912.814.616.518.320.122.023.825.627.529.331.1
91-------------6.18.110.312.214.115.917.819.721.523.425.227.128.930.8
92-------------5.47.59.811.713.515.417.319.221.122.924.826.728.530.4
93--------------6.89.211.113.014.916.818.720.622.524.426.328.230.1
94--------------6.28.710.612.514.416.318.220.222.124.025.927.829.7
95--------------5.68.110.012.013.915.817.819.721.623.625.527.429.4
96---------------7.59.511.413.415.317.319.221.223.225.127.129.0
97---------------7.08.910.912.914.916.818.820.822.724.726.728.7
98---------------6.48.410.412.414.416.418.320.322.324.326.328.3
99---------------5.87.99.911.913.915.917.919.921.924.026.028.0
100---------------5.37.39.311.413.415.417.519.521.523.625.627.7
101----------------6.88.810.912.915.017.019.121.123.225.327.3
102----------------6.28.310.412.414.516.618.620.722.824.927.0
103----------------5.77.89.911.914.016.118.220.322.424.526.7
104----------------5.27.29.311.513.615.717.819.922.124.226.3
TableRA3.2-2TargetSuperheat Return Air (Suction Wet-Bulb Line Temperature Temperature - (°F)(T Evaporator return, wb) Saturation Temperature)
Condenser Dry-Bulb Temperature (T cond. Air (°F) db)505152535455565758596061626364656667686970717273747576
90-------------6.88.810.912.814.616.518.320.122.023.825.627.529.331.1
91-------------6.18.110.312.214.115.917.819.721.523.425.227.128.930.8
92-------------5.47.59.811.713.515.417.319.221.122.924.826.728.530.4
93--------------6.89.211.113.014.916.818.720.622.524.426.328.230.1
94--------------6.28.710.612.514.416.318.220.222.124.025.927.829.7
95--------------5.68.110.012.013.915.817.819.721.623.625.527.429.4
96---------------7.59.511.413.415.317.319.221.223.225.127.129.0
97---------------7.08.910.912.914.916.818.820.822.724.726.728.7
98---------------6.48.410.412.414.416.418.320.322.324.326.328.3
99---------------5.87.99.911.913.915.917.919.921.924.026.028.0
100---------------5.37.39.311.413.415.417.519.521.523.625.627.7
101----------------6.88.810.912.915.017.019.121.123.225.327.3
102----------------6.28.310.412.414.516.618.620.722.824.927.0
103----------------5.77.89.911.914.016.118.220.322.424.526.7
104----------------5.27.29.311.513.615.717.819.922.124.226.3
105-----------------6.78.811.013.115.217.419.521.723.826.0
106-----------------6.28.310.512.614.817.019.121.323.525.7
107-----------------5.77.910.012.214.416.618.721.023.225.4
108-----------------5.27.49.511.713.916.118.420.622.825.1
109------------------6.99.111.313.515.718.020.222.524.7
110------------------6.48.610.813.115.317.619.922.124.4
111------------------5.98.110.412.614.917.219.521.824.1
112------------------5.47.69.912.214.516.819.121.523.8
113-------------------7.29.511.814.116.418.821.123.5
114-------------------6.79.011.413.716.118.420.823.2
Condenser (°F) (T Air Dry-Bulb Temperature cond., db)505152535455565758596061626364656667686970717273747576
79--------5.97.79.511.112.714.215.617.118.820.522.223.825.527.128.830.432.033.635.2
80---------6.98.710.412.013.515.016.618.320.021.723.325.026.728.329.931.633.234.8
81---------6.07.99.711.312.914.316.017.719.421.122.824.526.227.929.531.232.834.4
82---------5.27.18.910.612.213.715.417.218.920.622.324.025.727.429.130.732.434.0
83----------6.38.29.911.613.114.916.618.420.121.823.525.226.928.630.332.033.7
84----------5.57.49.210.912.514.316.117.819.621.323.024.826.528.229.931.633.3
85-----------6.68.510.311.913.715.517.319.020.822.624.326.027.829.531.232.9
86-----------5.87.89.611.313.215.016.718.520.322.123.825.627.329.130.832.6
87-----------5.07.08.910.612.614.416.218.019.821.623.425.126.928.730.432.2
88------------6.38.210.012.013.915.717.519.321.122.924.726.528.330.131.8
89------------5.57.59.411.513.315.117.018.820.622.424.326.127.929.731.5
Condenser Dry-Bulb Temperature (T cond. Air (°F) db)505152535455565758596061626364656667686970717273747576
115-------------------6.28.610.913.315.718.120.522.9

p.352Refrigerant scales shall be calibrated according to the manufacturer's recommended procedures. When the manufacturer certifies the calibration for a limited time, the refrigerant scale shall be recalibrated according to the manufacturers required procedure when the calibration period expires.

p.353ii. In all cases where the OEM instructions call for checking for gas leaks with

p.353nitrogen gas, the system was pressurized to the manufacturer’s specified pressure and if the pressure could not be maintained, leaks were located and fixed. No fittings (other than the fitting to the compressor) are compression or flare fittings.

p.355Shaded area requires return plenum temperature of 70°F or higher.

p.352Weigh-in Procedure

p.352The weigh-in procedure shall be performed in accordance with all manufacturer specifications to document and confirm:

p.353(b) The calculated weight adjustment for lineset length was based on the length and

p.353diameter of the lineset.

p.352(a) Liquid line filter drier has been installed if required per outdoor condensing unit

p.352manufacturer's instructions and installed with the proper orientation with respect to refrigerant flow.

p.353(c) The calculated weight adjustment for coil size was based on manufacturer instructions.

p.353(d) The actual charge adjustment was equal to the sum of the calculated weight adjustments

p.352(b) If refrigerant line connections require welding, the system is braised with dry nitrogen in

p.353for lineset and coil size.

p.352the lines and indoor coil.

p.353(e) The calculated and actual total weights of refrigerant in the system were recorded on or

p.352(c) In all cases where the OEM instructions call for checking for gas leaks with vacuum, the

p.353near the nameplate label, in indelible ink or other permanent means.

p.352system is evacuated to 500 microns or less and, when isolated, rises no more than 300 microns over five minutes.

p.352(d) In all cases where the OEM instructions call for checking for gas leaks with nitrogen gas,

p.352the system is pressurized to the manufacturer’s specified pressure and if the pressure cannot be maintained, leaks shall be located and fixed.

p.352(e) The calculated weight adjustment for lineset length is based on the length and diameter

p.352of the lineset.

p.352(f) The calculated weight adjustment for coil size is based on manufacturer instructions.

p.352(g) The actual total weight adjustment is equal to the sum of the calculated weight

p.352adjustments for lineset and coil size.

p.352(h) The calculated and actual total weights of refrigerant in the system are recorded on or

p.352near the nameplate label, in indelible ink or other permanent means.

p.352The HVAC Installer shall certify on the Certificate of Installation that the manufacturer's specifications for these procedures have been met. This shall be verified through on-site observation using procedures in RA 3.2.3.2.

p.354Appendix RA3– Residential Field Verification and Diagnostic Test Protocolsp.355

p.355Appendix RA3– Residential Field Verification and Diagnostic Test Protocolsp.356

p.356Appendix RA3– Residential Field Verification and Diagnostic Test Protocolsp.357

p.357Appendix RA3– Residential Field Verification and Diagnostic Test Protocolsp.358

p.358Appendix RA3– Residential Field Verification and Diagnostic Test Protocols

p.352RA3.2.3.2 ECC-Rater - Observation of Weigh-In Charging Procedure

p.352When the Standards indicate this procedure is required, or is an option for compliance, the ECC- Rater shall coordinate with the HVAC Installer to observe the weigh-in charging procedure.

p.352ECC-Rater shall observe and confirm:

p.352(a) Either 1) or 2) below:

p.3521. Observe and confirm Vacuum and Pressurization tests:

p.352Appendix RA3– Residential Field Verification and Diagnostic Test Protocolsp.353

p.353Appendix RA3– Residential Field Verification and Diagnostic Test Protocolsp.354