RA3.2.2.4 Calibration

p.346The accuracy of instrumentation shall be maintained using the following procedures. A sticker with the calibration check date shall be affixed to each instrument calibrated.

p.346RA3.2.2.4.1 Digital Thermometer and Temperature Sensor Field Calibration Procedure

p.346Thermometers with their temperature sensors shall be calibrated monthly to ensure that they are reading accurate temperatures.

p.346The following procedure shall be used to check thermometer/temperature sensor calibration:

p.346(a) Fill an insulated cup (foam) with crushed ice from distilled water. The ice shall completely

p.346fill the cup. Add distilled water to fill the cup.

p.346(b) Insert two sensors into the center of the ice bath and attach them to the digital

p.346thermometer.

p.346(c) Let the temperatures stabilize. The temperatures shall be 32 degrees Fahrenheit (plus or

p.346minus 1 degrees Fahrenheit). If the temperature is off by more than 1 degrees Fahrenheit, make corrections according to the manufacturer’s instructions. Any sensors that are off by more than 2 degrees Fahrenheit shall be replaced.

p.346(d) Switch the sensors and ensure that the temperatures read on both channels are still

p.346within plus or minus 1 degrees Fahrenheit of 32 degrees Fahrenheit.

p.346(e) Affix sticker with calibration check date onto sensor.

p.346(f) Repeat the process for all sensors.

p.346RA3.2.2.4.2 Digital Refrigerant Gauge Field Check Procedure

p.346Refrigerant gauges shall be checked monthly to ensure that the gauges are reading the correct pressures and corresponding temperatures. The following procedure shall be used to check gauge calibration:

p.346(a) Place a refrigerant cylinder in a stable temperature environment and let it acclimate for 4

p.346hours minimum to stabilize to the ambient conditions.

p.346(b) Attach a calibrated temperature sensor to the refrigerant cylinder using tape so that there

p.346is good contact between the cylinder and the temperature sensor.

p.346(c) Insulate over the temperature sensor connection to the cylinder.

p.346(d) Zero the low side and high side refrigerant gauges with all ports open to atmospheric

p.346pressure (no hoses attached).

p.346(e) Re-install the hoses, attach the high side gauge to the refrigerant cylinder, and open the

p.346valves to measure the pressure in the refrigerant cylinder.

p.346(f) Read the temperature of the sensor on the refrigerant cylinder.

p.346(g) Using a pressure/temperature chart for the refrigerant, look up the pressure that

p.346corresponds to the temperature measured.

p.346Appendix RA3– Residential Field Verification and Diagnostic Test Protocolsp.347

p.3472025 Residential Appendices (h) If gauge does not read the correct pressure corresponding to the temperature, the gauge

p.347is out of calibration and needs to be recalibrated.

p.347(i) Close the valve to the refrigerant cylinder, and bleed off a small amount of refrigerant to

p.347lower the high side pressure to give a corresponding temperature to between 45°F and 55°F.

p.347(j) Open the valves between the high side gauge and low side gauge.

p.347(k) If the two gauges corresponding refrigerant temperatures do not read within 1°F of each

p.347other, the low side gauge is out of calibration and needs to be recalibrated.

p.347(l) Affix sticker with calibration check date onto refrigerant gauge.