p.342RA3.2.2.1 Minimum Qualifications for this Procedure
p.342Persons who use this procedure to demonstrate compliance with Title 24 Part 6 shall be qualified to perform the following:
p.342(a) Obtain accurate system pressure and saturation temperature readings utilizing digital
p.342refrigeration gauges.
p.342(b) Obtain accurate temperature readings utilizing a digital thermometer and temperature
p.342sensors.
p.342(c) Check calibration of digital refrigerant gauges using a known reference pressure.
p.342(d) Check calibration of digital thermometer and temperature sensors using a known
p.342reference temperature.
p.342(e) Determine the required or best location for temperature measurements in duct systems
p.342and on refrigerant lines.
p.342(f) Calculate the measured superheat and subcooling.
p.342(g) Determine the required superheat, based on the conditions present at the time of the
p.342test.
p.342(h) Determine if measured values are accurate.
p.342RA3.2.2.2 Instrumentation Specifications
p.342Instrumentation for the procedures described in this section shall conform to the following specifications:
p.342RA3.2.2.2.1 Digital Temperature Measurement Specifications
p.342Temperature measurements shall be made utilizing digital temperature measurement instrumentation (combined sensor plus device for data acquisition, processing, and reporting) that shall have dual channel capability in Celsius or Fahrenheit and conform to the following specifications:
p.342Appendix RA3– Residential Field Verification and Diagnostic Test Protocolsp.343
p.3432025 Residential Appendices RA3.2.2.2.1.1 Dry-bulb Air Temperature Measurements