p.329For use in establishing the target duct leakage rate compliance criteria, the system air handler airflow shall be calculated using RA3.1.4.2.1, RA3.1.4.2.2, or RA3.1.4.2.3 as applicable.
p.329RA3.1.4.2.1 Default Air Handler Airflow
p.329Default air handler airflow may be used for any one of the following conditions:
p.329(a) for heating-only systems, or
p.329(b) when a duct system is being tested prior to installation of the air conditioning or heating
p.329system equipment, or
p.329(c) when the space conditioning system equipment specification is not known.
p.329Default air handler airflow shall be a calculated value equal to 0.5 CFM per ft2 of Conditioned Floor Area.
p.329RA3.1.4.2.2 Nominal Air Handler Airflow
p.329Nominal air handler airflow shall be calculated according to one of the following methods as applicable:
p.329(a) For heating-only systems, the nominal air handler airflow shall be 21.7 CFM per kBtu/hr of
p.329rated heating output capacity.
p.329(b) For split or packaged cooling systems with only one indoor unit, the nominal air handler
p.329airflow shall be 400 CFM per nominal ton of outdoor condensing unit cooling capacity as specified by the manufacturer.
p.329(c) For small duct high velocity systems, the nominal air handler airflow shall be 250 CFM per
p.329nominal ton of outdoor condensing unit cooling capacity as specified by the manufacturer.
p.329(d) For multiple-split systems that provide cooling, the nominal air handler airflow for each
p.329indoor unit shall be 350 CFM per nominal ton of indoor unit cooling capacity as specified by the manufacturer.
p.329RA3.1.4.2.3 Measured System Airflow
p.329The system airflow shall be as measured according to a procedure in Section RA3.3.3. The system airflow can be used as the air handler airflow for the purpose of establishing duct leakage percentage.
p.329RA3.1.4.3 Diagnostic Duct Leakage
p.329Diagnostic duct leakage measurement is used by installers and raters to verify that total leakage meets the criteria for any sealed duct system specified in the compliance documents.
p.329When central fan integrated (CFI) indoor air quality ventilation system air ducts, or central fan ventilation cooling system (CFVCS) air ducts connect to space conditioning system ducts, the ventilation duct branch openings shall not be sealed/taped off during space conditioning system
p.329Appendix RA3– Residential Field Verification and Diagnostic Test Protocolsp.330
p.3302025 Residential Appendices duct leakage testing. However, the ventilation system motorized dampers that open only when ventilation airflow is required and close when ventilation airflow is not required may be closed during space conditioning system duct l eakage testing.
p.330Table RA3.1-2 summarizes the leakage test procedures that may be used to demonstrate compliance.
p.330Table RA3.1-2 – Duct Leakage Verification and Diagnostic Test Protocols
p.330Verification Description User Application Procedure(s)
p.330Sealed and tested new duct systems in single Installer Testing at Final RA3.1.4.3.1 family homes and townhomes ECC-Rater Testing
p.330Sealed and tested new duct systems in single Installer Testing at Rough-in, RA3.1.4.3.2 family homes and townhomes Air Handling Unit Installed RA3.1.4.3.2.1 RA3.1.4.3.3
p.330Sealed and tested new duct systems in single Installer Testing at Rough-in, RA3.1.4.3.2 family homes and townhomes Air Handling Unit Not RA3.1.4.3.2.2 Installed RA3.1.4.3.3
p.330Sealed and tested new duct systems in Installer Testing at Final RA3.1.4.3.1 multifamily homes regardless of duct system ECC-Rater Testing location.
p.330Sealed and tested new duct systems in Installer Testing at Final RA3.1.4.3.4 multifamily homes regardless of duct system ECC-Rater Testing location.
p.330Verification of Low Leakage Air Handler with Installer Testing at Final RA3.1.4.3.1 and Sealed and Tested Duct System Compliance ECC-Rater Testing RA3.1.4.3.9 Credit
p.330Verification of low leakage ducts located Installer Testing RA3.1.4.3.8 entirely in conditioned space ECC-Rater Testing
p.330Sealed and tested altered existing duct Installer Testing RA3.1.4.3.1 systems ECC-Rater Testing
p.330Sealed and tested altered existing duct Installer Testing RA3.1.4.3.4 systems ECC-Rater Testing
p.330Sealed and tested altered existing duct Installer Testing and RA3.1.4.3.5 systems Inspection RA3.1.4.3.6 ECC-Rater Testing and RA3.1.4.3.7 Verification