p.3282025 Residential Appendices RA3.1.4.1.7 Verification of Space-Conditioning System Airflow Supply to All Habitable Spaces
p.328A visual inspection shall confirm that all habitable spaces in the dwelling unit receive space- conditioning system airflow either by use of a ductless space-conditioning system indoor unit located on the wall, ceiling, or floor of the habitable space, or by use of space-conditioning system air supply registers located in the habitable space that use ductwork connected from the register directly to the supply air outlet of a ducted space-conditioning system air handling unit. Refer to Standards Section 100.1 for the definition of habitable space. Transfer fans that move air from one space in the dwelling to a different space in the dwelling, but do not heat or cool the air transferred, do not meet the requirement for providing space-conditioning system airflow.
p.328RA3.1.4.1.8 Verification of Ductless Space-Conditioning System Indoor Units Located
p.328Entirely in Conditioned Space
p.328A visual inspection shall confirm that ductless indoor units are located entirely in conditioned space in accordance with the following requirements:
p.328(a) Ductless indoor unit types that mount entirely on the interior surface of dwelling unit
p.328walls, ceilings, or floors shall be considered to be entirely in conditioned space. Penetrations in the wall, ceiling, or floor surface necessary for the indoor unit refrigerant piping, condensate drain, or electrical connections shall be allowed, provided the penetrations are sealed.
p.328(b) Ductless indoor units that penetrate the interior surface of dwelling unit walls, ceilings, or
p.328floors, and protrude through cut-out openings in the dwelling unit walls, ceilings, or floors shall be inspected to determine whether the indoor unit is installed inside both the thermal boundary and the air barrier of the dwelling according to the following criteria as applicable:
p.328i. Ductless indoor units that protrude through the air barrier into unconditioned spaces
p.328(including but not limited to attics, crawl spaces, garages, or outdoors) are not located entirely in conditioned space.
p.328ii. Ductless indoor units that protrude into indirectly conditioned spaces (including but
p.328not limited to drop ceilings, or floor assemblies in a single family or multifamily multi story building) that are wholly inside both the thermal boundary, and the air barrier of the dwelling are located entirely in conditioned space. Note: Verification at an early stage of building construction may be necessary for visual verification to be possible.
p.328If field verification according to RA3.1.4.1.8 determines the installed system's ductless indoor units are not located entirely in conditioned space, then the system does not comply with the VCHP compliance option eligibility requirements.
p.328Appendix RA3– Residential Field Verification and Diagnostic Test Protocols