p.543NA7.5.11.1 Construction Inspection
p.543Prior to Functional Testing, verify and document the following:
p.543(a) Verify fault detection and diagnostics (FDD) hardware is installed on HVAC unit.
p.543(b) Verify the FDD system matches the make and model reported on the design
p.543drawings.
p.543(c) Verify the following air temperature sensors are permanently installed:
p.5431. Outside air.
p.5432. Supply air.
p.5433. Return air.
p.543(d) Verify the controller has the capability of displaying the value of the following
p.543parameters:
p.5431. Air temperatures: outside air, supply air, return air.
p.543(e) Verify the controller provides system status by indicating the following conditions:
p.5431. Free cooling available.
p.5432. Economizer enabled.
p.5433. Compressor enabled.
p.5434. Heating enabled.
p.5435. Mixed air low limit cycle active.
p.543NA7.5.11.2 Functional Testing
p.543For each HVAC unit to be tested, complete the following:
p.543NA7.5.11.2.1Functional Testing for Air Temperature Sensor Failure/Fault
p.543Step 1: Verify the FDD system indicates normal operation.
p.543Step 2: Disconnect outside air temperature sensor from unit controller. Verify and
p.543document the following:
p.543(a) FDD system reports a fault.
p.543Step 3: Connect outside air temperature sensor to unit controller. Verify and document
p.543the following:
p.543(b) FDD system indicates normal operation.
p.543NA7.5.11.2.2Functional Testing for Excess Outside Air
p.543Step 1: Coordinate this test with NA7.5.1 Outdoor Air.
p.543(a) If NA7.5.1 Outdoor Air passes, verify FDD system indicates normal operation.
p.543Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processesp.544
p.5442025 Nonresidential Appendices NA7.5.11.2.3Functional Testing for Economizer Operation