NA7.10.4 Variable Speed Screw Compressors

p.585NA7.10.4 Variable Speed Screw Compressors

p.585Conduct and document the following functional tests on all variable-speed screw compressors.

p.585NA7.10.4.1 Construction Inspection

p.585Prior to functional testing, document the following:

p.585(a) Verify all single open-drive screw compressors dedicated to a suction group have

p.585variable speed control.

p.585(b) Verify all compressor suction and discharge pressure sensors read accurately (or

p.585provide an appropriate offset) using a standard.

p.585(c) Verify all input or control temperature sensors used by controller read accurately

p.585(or provide an appropriate offset) using temperature standard.

p.585(d) Verify that all sensor readings used by the compressor controller convert or

p.585calculate to the correct conversion units at the controller (e.g., saturated pressure reading is correctly converted to appropriate saturated temperature, etc.).

p.585(e) Verify that all compressor speed controls are operational and connected to

p.585compressor motors.

p.585(f) Verify that all speed controls are in “auto” mode.

p.585Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processesp.586

p.5862025 Nonresidential Appendices (g) Verify that compressor panel control readings for “RPMs,” “% speed,” “kW”, and

p.586“amps” match the readings from the PLC or other control systems.

p.586(h) Verify that compressor nameplate data is correctly entered into the PLC or other

p.586control system.