p.582NA7.10.3.3 Adiabatic Condensers and Condenser Fan Motor Variable Speed Control
p.582Conduct and document the following functional tests on all adiabatic condensers.
p.582NA7.10.3.3.1Construction Inspection
p.582Prior to functional testing, document the following:
p.582(a) Verify the control system minimum Saturated Condensing Temperature (SCT)
p.582setpoint is at or below 70°F.
p.582(b) Verify the control system maximum SCT setpoint (if used) is at or near the system
p.582design SCT.
p.582(c) Verify accuracy of refrigerant pressure-temperature conversions and consistent
p.582use of either temperature or pressure for the controlled variable setpoint in the control system.
p.582(d) Verify the discharge pressure sensor (or condenser pressure if used) reads
p.582accurately, using a National Institute of Standards and Technology (NIST) traceable reference pressure gauge or meter. At the minimum, the discharge pressure sensor accuracy shall be verified at two different pressures within the typical operating range. Calibrate if needed. Replace if outside manufacturer’s recommended calibration range.
p.582Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processesp.583
p.5832025 Nonresidential Appendices (e) Verify the ambient dry bulb temperature using a NIST traceable instrument,
p.583including verification of at least two different ambient readings. Calibrate if needed. Replace if outside manufacturer’s recommended calibration range.
p.583(f) Verify all ambient dry bulb temperature sensors are not mounted in direct sunlight
p.583or is provided within a suitable solar shield.
p.583(g) Verify that all sensor readings used by the condenser controller convert or
p.583calculate to the correct conversion units and are displayed at the controller (e.g., observed pressure reading is correctly converted to appropriate saturated temperature, etc.).
p.583(h) Verify that all fan motors are operational and rotating in the correct direction.
p.583(i) Verify that all condenser fan speed controls operate automatically in response to
p.583changes in both pressure (SCT) and ambient temperature.