p.4782025 Nonresidential Appendices NA1.6.2 Procedures - Initial Field Verification and Diagnostic Testing
p.4792025 Nonresidential Appendices shall be submitted to the Provider but are not required to be registered, in preparation for potential future quality assurance audits. The group shall be closed prior to selection of the sample that will be field verified and diagnostically tested.
p.478The ECC-Rater shall diagnostically test and field verify the first system or dwelling unit of each building when the builder elects to demonstrate verification compliance utilizing group sampling. This initial testing allows the builder to identify and correct any potential construction flaws or practices in advance of subsequent further installations. If field verification and diagnostic testing determines that the requirements for compliance are met, the ECC-Rater shall transmit the test results to the ECC-Provider registry, whereupon the Provider shall make available a copy of the registered Certificate of Verification to the ECC- Rater, the builder, and the enforcement agency.
p.479The builder or the ECC-Rater may request removal of units from the group by notifying the ECC-Provider prior to selection of the sample that will be tested and shall provide justification for the change. Removed units which are installed shall either be field verified and diagnostically tested individually or shall be included in a subsequent group for sampling.
p.479The ECC-Rater, with no direction from the installer, builder, or owner shall randomly select one system or dwelling unit from the “closed” group for field verification and diagnostic testing upon receiving the builder’s or builder representative’s request for verification of that group. The ECC-Rater shall enter the test and/or field verification results into the Data Registry regardless of whether the results indicate a pass or fail. If the test fails, then the failure must be entered into the Provider’s Data Registry even if the installer immediately corrects the problem. In addition, the procedures in NA1.6.4 shall be followed.
p.478NA1.6.3 Procedures -– Group Sample Field Verification and Diagnostic Testing
p.478After the initial field verification and diagnostic testing is completed, the builder or the ECC- Rater shall identify a group of up to seven individual systems or dwelling units in the building from which a sample will be selected and identify the names and license numbers of the subcontractors responsible for the installations requiring field verification and diagnostic testing. The date the first system or dwelling unit in the group is identified shall establish the start date for the new opened sample group. The ECC-Provider shall record and track the start date for each sample group.
p.479If field verification and diagnostic testing determines that the requirements for compliance are met, the ECC-Rater shall enter the test results into the Data Registry. Whereupon, the Provider shall make available to the ECC-Rater, the builder, the enforcement agency and other approved users of the Data Registry, a copy of the registered Certificate of Verification for the “tested” system or dwelling unit and a Certificate of Verification shall also be provided for each “not tested” system or dwelling unit in the sample group. The Certificate of Verification shall report the successful diagnostic testing results and conclusions regarding compliance for the “tested” system or dwelling unit. The Certificate of Verification shall also provide:
p.478If dwelling units have multiple measures requiring verification installed, each dwelling unit in a designated group shall have the same measures requiring verification as the other dwelling units in the designated group. If some dwelling units have installed a different set of measures requiring verification, those dwelling units shall be in a separate group.
p.478If the dwelling units in a designated group have multiple measures that require verification, sample testing for individual measures may be conducted in any of the dwelling units in the group - it is not required that all of the sample tests for all of the individual measures be completed in the same dwelling unit. Individual measures shall be allowed to be included in a group regardless of whether compliance requires one sample test, or if compliance requires more than one sample test (up to100% sample test rate) be reported for such individual measures.
p.479(a) Building permit number for the unit.
p.479(b) Registration Number – that conforms to the numbering convention specified in
p.479Reference Joint Appendix JA7.
p.479(c) Group Number – that conforms to the numbering convention specified in Reference
p.479Joint Appendix JA7.
p.478If dwelling units have central forced-air space conditioning equipment that introduces outside air into the conditioned space utilizing means that connect outside air ventilation ducts directly to the dwelling unit’s central forced air duct system (Central Fan-Integrated Ventilation System or CFI Ventilation System), the CFI ventilation technology shall be considered a separate measure for verification sampling purposes, and dwellings with CFI ventilation systems shall be placed in separate groups from other dwelling units that do not utilize CFI ventilation technology.
p.479(d) Time and date stamp of the Provider’s issuance of the registered Certificate of
p.479Verification.
p.479(e) Provider’s logo, water mark, or official seal.
p.479(f) Indication that the conditioning unit was a “tested” unit or was a “not tested” unit from
p.479the sample group.
p.479The registered Certificate of Verification shall not be provided for measures that have not yet been installed.
p.478For newly constructed buildings, systems or dwelling units in a designated group shall all be located within the same enforcement agency jurisdiction. Refer to Section NA1.8 for requirements for sample groups applicable to alterations.
p.479Whenever the builder changes subcontractors who are responsible for installation of the systems or dwelling unit measures, the builder shall notify the ECC-Rater of the subcontractor change and terminate sampling for any affected group. All units requiring ECC-Rater field verification and diagnostic testing for compliance that were installed by previous subcontractors or were subject to field verification and diagnostic testing under the supervision of a previous ECC-Provider, for which the builder does not have a completed Certificate of Verification, shall either be individually tested or included in a separate group
p.478The ECC-Rater shall verify that a Certificate of Compliance, a Certificate of Installation, and a Certificate of Acceptance have been completed for each unit having features requiring verification. The ECC-Rater shall also confirm that the Certificate of Installation and Certificate of Acceptance have been completed as required, and that the field technician’s diagnostic test results and all other Certificate of Acceptance information shows compliance consistent with the Certificate of Compliance. The Certificates of Acceptance for each group
p.478Appendix NA1– Nonresidential Verification, Testing, and Documentation Proceduresp.479
p.479Appendix NA1– Nonresidential Verification, Testing, and Documentation Procedures