p.4742025 Nonresidential Appendices units from a designated group for which compliance is verified based on the results of a sample test. The registered Certificates of Verification shall be made available to the ECC- Rater, the builder, the enforcement agency, and to other authorized users of the ECC- Provider data registry.
p.474The ECC-Rater shall produce a separate Certificate of Verification for each system that meets the diagnostic requirements for compliance. The registered Certificate of Verification shall have unique ECC-Provider-designated identifiers for registration number, and sample group number, and shall include the lot location, building permit number, time and date stamp of issuance of the certificate, Provider logo or seal, and indicate if the space conditioning unit has been “tested or if it was a “not tested” unit approved as part of sample group. The ECC-Rater shall not provide a Certificate of Verification for a building with a space conditioning unit that does not have a completed signed Certificate of Installation as specified in Section NA1.4 and Certificate of Acceptance as specified in Section NA1.5.
p.474If field verification and diagnostic testing on a sampled space conditioning unit identifies a failure to meet the requirements for compliance credit, the ECC-Rater shall report to the ECC-Provider, the builder, and the enforcement agency that re-sampling will be required.
p.474If re-sampling identifies another failure, the ECC-Rater shall report to the ECC-Provider, the builder, and the enforcement agency that corrective action, diagnostic testing, and field verification will be required for all the untested space conditioning units in the group. The report shall identify each space conditioning unit that shall be fully tested and corrected.
p.474The ECC-Provider shall also report to the builder when diagnostic testing and field verification has shown that the failures have been corrected for all of the space conditioning units.
p.474When individual space conditioning unit testing and verification confirms that the requirements for compliance have been met, the ECC-Provider shall make available to the builder and the enforcement agency a registered copy of the Certificate of Verification for each space conditioning unit in the group.
p.474The ECC-Provider shall file a report with the enforcement agency if there has been a sample group failure, explaining all actions taken (including field verification, testing, and corrective actions) to bring into compliance space conditioning units for which full testing has been required.
p.474NA1.3.3 Third-Party Quality Control Program
p.474Third Party Quality Control Programs (TPQCP) verify the work of participating installers, collect and evaluate more detailed data than necessary for compliance, identify in real time during the installation invalid and inaccurate installer testing and noncompliant installations, and enable corrected testing with the goal of bringing installations into compliance before the installer leaves the job site. TPQCP personnel and participating TPQCPs do not sign Certificate of Verification documentation, given that they provide assistance and quality control to ECC-Raters, who remain responsible for this documentation.
p.474An approved Third Party Quality Control Program shall:
p.474(a) Provide training to participating program installers, installing but not limited to
p.474contractors, subcontractors, and technicians, to ensure proficiency in:
p.474Appendix NA1– Nonresidential Verification, Testing, and Documentation Procedures