RA3.1.4.1.1 Verified Duct System Design

p.326An installed duct system meets the Verified Duct System Design compliance criteria if it is field verified by a ECC-rater to be in conformance with a duct design layout that meets all applicable duct design and documentation requirements given in Section RA3.1.4.1.1. The duct design layout shall be approved by the enforcement agency.

p.326RA3.1.4.1.1.1 Verified Duct System Design - Duct Design Layout

p.326The duct system design shall be documented on the Duct Design Layout, a scaled layout drawing that identifies the location of the space conditioning equipment, all supply and return registers/grilles, the size, R-value, and location of each duct segment. The Duct Design Layout shall incorporate all other duct details reported on the registered Certificate of Compliance.

p.326RA3.1.4.1.1.2 Verified Duct System Design - Compliance Criteria

p.326The duct system design shall be based on an industry standard design methodology such as ACCA Manual D, or an equivalent, and shall take into account: the available external static pressure from the air handler, the equivalent length or pressure drop of external devices, and the pressure drop of the duct runs accounting for size, type and configuration of the ducts and fittings. The duct system shall be designed to meet the required system airflow rate with the manufacturer- specified available external static pressure for the specified system air handler at that airflow. The duct system design shall include calculations that indicate the duct system will operate at equal to or greater than 0.0292 cfm/Btu (350 cfm/12000 Btu) in cooling speed (350 cfm per nominal ton of condensing unit cooling capacity specified by the manufacturer) or, if heating only, equal to or greater than 16.8 cfm per 1000 Btu/hr furnace nominal output specified by the manufacturer.

p.326RA3.1.4.1.1.3 Verified Duct System Design - Duct Design Layout Approval

p.326The Duct Design Layout shall be included with the building design plans and the registered Certificate of Compliance submitted to the enforcement agency in conjunction with the application for the building permit. A copy of the Duct Design Layout approved by the enforcement agency shall be posted or made available with the building permit(s) issued for the building, and shall be made available to the enforcement agency, installing contractor, and ECC- rater for use during the installation work and for all applicable inspections.

p.326RA3.1.4.1.1.4 Verified Duct System Design - Field Verification of Installation

p.326The location of all supply and return registers shall be verified by inspection of the interior of the dwelling unit. The location of the space conditioning equipment and the size, R-value, and location of each duct segment shall be verified by observation in the spaces where they are located. Deviations from the approved Duct Design Layout shall not be allowed without a revised a Duct Design Layout approved by the enforcement agency.

p.326Appendix RA3– Residential Field Verification and Diagnostic Test Protocolsp.327

p.3272025 Residential Appendices RA3.1.4.1.2 Verification of 12 Linear Feet or Less of Duct Located Outside Of Conditioned Space