p.4492025 Residential Appendices (d) When the water pump is running, verify that all the condenser coils are wet.
p.449(e) Verify that the high pressure trip for the compressor is set (per manufacturer’s
p.449specifications) at or below 300 psig for R22 Refrigerant and at or below the saturation pressure corresponding to a temperature of 1310 F for all other refrigerants.
p.449(f) Turn off the water supply to the water casing, drain the water from the sump, and verify
p.449that the water pump and the compressor trip.
p.449(g) Verify that the condenser coils have a corrosion resistant coating and that the water
p.449casing is made up of corrosion resistant material.
p.449(h) Verify that the electrolytic protection is installed.
p.449(i) Verify that a blow-down pump is installed for periodic blow-down to remove solids from
p.449the water casing.
p.449(j) Verify that the operation of this pump is automatic based on compressor run time or
p.449the conductivity of the water in the casing.
p.449(k) Verify that the water casing is sloped downward towards the blow-down pump location
p.449to facilitate removal of solids.
p.449(l) Drift eliminators must be installed to reduce the loss of water to less than 0.002% of
p.449the recirculated water (as per test method CTI-HBIK Std.140 or other approved procedure).
p.449(m) Condensate water must be routed to the evaporative condenser sump, unless it is not
p.449practical, i.e., the fan coil and condenser not separated by conditioned space.
p.449(n) Condenser must have a certification from the manufacturer that water consumption is
p.449less than 0.15 gph per ton of capacity.
p.449(o) Water connection is made with tubing no large than 1/4 inch diameter.
p.449(p) Overflow from the unit is not connected directly to the sewer drain (son in the event of
p.449a water float failure an overflow condition can be more easily detected) or another means of determining an overflows condition is provided.
p.449(q) The system has a backup solenoid water shutoff control or no spill sump.
p.449RA4.3.2 Evaporative Cooling
p.449Qualifying equipment is limited to either indirect-direct or indirect evaporative coolers. Direct evaporative coolers and indirect or indirect-direct evaporative coolers that do not meet the following eligibility criteria shall not be used.
p.449RA4.3.2.1 Eligibility Testing
p.449The installing contractor shall complete the following eligibility testing and document the results on the applicable Certificate of Installation.
p.449(a) Eligible equipment shall be listed under Title 20 Appliance Standards.
p.449– Eligibility Criteria for Energy Efficiency Measures