p.422RA3.5.8.3 Roof/Ceilings
p.422(a) Baffles shall be placed at eaves or soffit vents of vented attics to keep insulation from
p.422blocking eave ventilation and prevent air movement under the insulation. The required net- free ventilation shall be maintained.
p.422(b) Hard covers or draft stops shall be placed over all drop ceiling areas and interior wall cavities
p.422to keep insulation in place and stop air movement. If hard covers or draft stops are missing or incomplete, they shall be completed before insulation is installed.
p.422(c) In traditional framed attics, required eave ventilation shall not be obstructed for conventional
p.422attics - the net free-ventilation area of the eave vent shall be maintained. Eave vent baffles shall be installed to prevent air movement under or into the ceiling insulation of conventional attics.
p.422(d) Insulation shall cover all recessed lighting fixtures. If the fixtures are not rated for insulation
p.422contact (IC) and airtight, the fixtures shall be removed and/or replaced.
p.422(e) All recessed light fixtures that penetrate the ceiling shall be listed for zero clearance
p.422insulation contact (IC), have a label that certifies it as airtight with leakage less than 2.0 cfm @ 75 Pa when tested to ASTM E283, and shall be sealed with a gasket or caulk between the light's housing and the ceiling.
p.422RA3.5.8.3.1 Special Situations--Attics and Cathedral Ceilings
p.422Insulation installed in unvented rafter ceilings or to the underside of unvented roofs with an attic below shall have an R-value conforming to compliance documentation and the air barrier shall be uniform across the transition of roof to wall. The insulation shall be in contact with the air barrier.
p.422RA3.5.8.3.2 Special Situations--HVAC Platform
p.422Insulation shall be placed below any platform or catwalk for HVAC equipment installation and access.
p.422RA3.5.8.3.3 Special Situations--Attic Access
p.422Permanently attach rigid board insulation, batt, or blanket insulation with the appropriate R- value to the access door using adhesive or mechanical fastener. The bottom of the attic access shall be gasketed to prevent air leakage of conditioned air to the unconditioned attic.
p.422RA3.5.8.4 Raised Floors
p.422The outer and inner face, and all joints of the ICF air barrier, shall be maintain through use of tape, or sealing and caulking as needed.
p.422– Residential Field Verification and Diagnostic Test Protocolsp.423
p.4232025 Residential Appendices RA3.5.8.4.1 Homes with Floors Over Garage