p.310RA2.6.2 ECC-Rater Procedures - Initial Model Field Verification and Diagnostic Testing
p.310The ECC-Rater shall diagnostically test and field verify the first dwelling unit of each model within a subdivision or multifamily housing development when the builder elects to demonstrate verification compliance utilizing group sampling. To be considered the same model, dwelling units shall have the same basic floor plan layout, energy design, and compliance features as shown on the Certificate of Compliance. Variations in the basic floor plan layout, energy design, compliance features, zone floor area, or zone volume, that do not change the features to be tested, the heating or cooling capacity of the HVAC unit(s), or the number of HVAC units specified for the dwelling units, shall not cause dwelling units to be considered a different model. For multifamily buildings, variations in exterior surface areas caused by location of dwelling units within the building shall not cause dwelling units to be considered a different model. This initial model testing allows the builder to identify and correct any potential construction flaws or practices in advance of the build out of each model. If field verification and diagnostic testing determines that the requirements for compliance are met, the ECC-Rater shall transmit the test results to the ECC-Provider data registry, whereupon the Provider shall make available a registered copy of the Certificate of Verification, to the ECC-Rater, the builder, the enforcement agency, and other authorized users of the ECC-Provider data registry.
p.310RA2.6.3 ECC-Rater Procedures – Group Sample Field Verification and Diagnostic Testing
p.310Descriptions for verification compliance using group sampling, and details describing procedures for sampling of a “closed” group of up to seven dwellings, and for sampling of an “open” group of up to five dwellings are described in Section RA2.6.3.
p.310RA2.6.3.1 Designation of Groups
p.310After the initial model field verification and diagnostic testing is completed as specified in RA2.6.2, the builder, or the builder’s authorized representative shall determine a sampling procedure to be used and shall designate the dwelling units to include in the group of dwellings that require verification. The maximum number of dwelling units allowed in a sample group may range from five, to seven, to thirty as described in Sections RA2.6.3.3, RA2.6.3.4, and RA2.7 respectively.
p.310If multiple measures requiring verification are installed, each dwelling unit in a designated group shall have the same measures requiring verification as the other dwelling units in the designated
p.310Appendix RA2– Residential Field Verification and Diagnostic Testing Documentation Proceduresp.311
p.3112025 Residential Appendices group. If some dwelling units have installed a different set of measures requiring verification, those dwelling units shall be in a separate group.
p.311If the dwelling units in a designated group have multiple measures that require verification, sample testing for individual measures may be conducted in any of the dwelling units in the group - it is not required that all of the sample tests for all of the individual measures be completed in the same dwelling unit. Individual measures shall be allowed to be included in a group regardless of whether compliance requires one sample test, or if compliance requires more than one sample test (up to100% sample test rate) be reported for such individual measures.
p.311Dwelling units in a designated group shall all be located within the same enforcement agency jurisdiction and subdivision or multifamily housing development. Refer also to Section RA2.8 for requirements for sample groups applicable to alterations.
p.311If dwelling units have central forced-air space conditioning equipment that introduces outside air into the conditioned space utilizing means that connect outside air ventilation ducts directly to the dwelling unit’s central forced air duct system (Central Fan-Integrated Ventilation System or CFI Ventilation System), the CFI ventilation technology shall be considered a separate measure for verification sampling purposes, and dwellings with CFI ventilation systems shall be placed in separate groups from other dwelling units that do not utilize CFI ventilation technology.