p.2912025 Residential Appendices Definition - Condenser Outlet Air Restrictor: A device which restricts the free area of the outlet from the condenser fan to reduce the air flow but does not interfere with air entering the condenser coil. The amount of restriction shall be adjustable to allow the operator to vary the airflow to achieve the target refrigerant pressure difference.
p.2922025 Residential Appendices Similar to the Standard Charge Verification Procedure for warm weather, the Winter Charge Setup requires that the return air dry bulb temperature must be maintained within the manufacturer's specification during the test, as specified in RA3.2.2. Suggestions for methods to accomplish warmer return air are posted on the Energy Commission website at the following link:
p.2932025 Residential Appendices
p.292http://www.energy.ca.gov/title24/orc/hvac/Similar to the Standard Charge Measurement Procedure for warm weather, the Winter Charge Setup procedure does not relieve the installing contractor from any obligations to follow manufacturers’ specifications. The procedures in Section RA1.2 are used to demonstrate compliance with Title 24, Part 6 requirements for refrigerant charge verification.p.293
p.291RA1.2.2 Winter Setup for the Standard Charge Verification Procedure
p.291a) Install the condenser outlet air restrictor on the outlet from the condenser fan:
p.291Position the restrictor so it does not interfere with the inlet airflow to the condenser.
p.291Start the air conditioner or heat pump in the cooling mode and restrict the outlet until the difference between the high side pressure and the low side pressure is between 160 psi and 220 psi for R-410A refrigerant and 100 to 145 psi for R-22 refrigerant.
p.293(This page intentionally left blank.)p.294
p.291160 psi ≤ (Phigh, – Plow ) ≤ 220 psi for R-410A refrigerant; 100 psi ≤ (Phigh, – Plow ) ≤ 145 psi for R-22 refrigerant
p.291Allow the unit to stabilize for 15 minutes, watching the pressures to make sure the differential achieves and remains within 160 psi ≤ (Phigh, – Plow ) ≤ 220 psi for R-410A refrigerant.
p.291100 psi ≤ (Phigh, – Plow ) ≤ 145 psi for R-22 refrigerant
p.291b) Follow the test procedures specified in the Reference Residential Appendix, Section
p.291RA3.2.2.6.2, Variable Metering Device Calculations to determine compliance.
p.291RA1.2.3 Additional Requirements and Qualifications
p.291The Winter Charge Setup may only be used for equipment for which the air conditioning manufacturer approves the use of the Winter Charge Setup. Refer to the Energy Commissions website for the list of split system air conditioner units approved by the manufacturers to use the Winter Charge Setup. In addition to the requirements of Section RA1.2, manufacturers may issue additional instructions/clarification for the equipment and procedures required to be used to conduct the Winter Charge Setup. These additional instruction/clarifications shall also be available on the Energy Commission website: www.energy.ca.gov/title24/.
p.291Winter Charge Setup may be used for systems that use a target subcooling for refrigerant charge verification, including units equipped with micro-channel heat exchangers where the manufacturer specifies subcooling for measuring refrigerant charge.
p.291Similar to the Standard Charge Verification Procedure for warm weather, the Winter Charge Setup may be used by the Installer and/or the ECC-Rater.
p.291The system shall comply with the minimum system airflow requirements specified in Reference Residential Appendix Section RA3.3.3.1.p.292
p.291- Alternative Residential Field Verification and Diagnostic Test Protocols
p.292- Alternative Residential Field Verification and Diagnostic Test Protocols
p.293- Alternative Residential Field Verification and Diagnostic Test Protocols