NA7.8.1.2 Functional Testing

p.5752025 Nonresidential Appendices (b) Motion sensor is located to minimize false signals.

p.575(c) Desired sensor coverage is not blocked by obstructions that could adversely affect

p.575performance.

p.575NA7.8.1.2 Functional Testing

p.575For building sites with up to seven (7) motion sensors, all motion sensors shall be tested. For sites with more than seven (7) motion sensors, sampling may be done on outdoor areas with similar sensors that cover similar unobstructed areas; sampling shall include a minimum of 1 motion sensor for each group of up to 7 additional motion sensors.

p.575If the first sensor in the sample group passes the acceptance test, the remaining outdoor areas in the sample group also pass. If the first motion sensor in the sample group fails the acceptance test, the rest of the sensors in that group shall be tested and any failed sensor in the sample group shall be repaired or replaced and retested until the sensor passes the test.

p.575Step 1: Simulate motion in area under luminaire controlled by the motion sensor. Verify

p.575and document the following:

p.575(a) Status indicator operates correctly.

p.575(b) Luminaires controlled by sensors turn on immediately upon entry into the area lit

p.575by the controlled luminaires near the sensor.

p.575(c) Signal sensitivity is adequate to achieve desired control.

p.575Step 2: Simulate no motion in area with lighting controlled by the motion sensor.

p.575Verify and document the following:

p.575(a) The controlled luminaires are turned off or the lighting power of each controlled

p.575luminaire is reduced by at least 50 percent and no more than 90 percent within a maximum of 15 minutes from the start of an unoccupied condition.

p.575(b) The sensor does not trigger a false “on” from movement outside of the controlled

p.575area.

p.575(c) Signal sensitivity is adequate to achieve desired control.

p.575NA7.8.2 Photocontrols Acceptance Tests

p.575NA7.8.2.1 Construction Inspection

p.575Verify and document the following:

p.575The photocontrols are shown on plan documents and are installed.

p.575NA7.8.2.2 Functional Testing

p.575For building sites with up to seven (7) photosensors, all photosensors shall be tested. For sites with more than seven (7) photosensors, sampling may be done on outdoor areas with similar photosensors that cover similar unobstructed areas; sampling shall include a minimum of 1 photosensors for each group of up to 7 additional photosensors.

p.575Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes