NA7.5.3.2.3.2 Diagnostic Duct Leakage

p.535NA7.5.3.2.3.2 Diagnostic Duct Leakage

p.535Diagnostic duct leakage measurement shall be used by installers and ATTs to verify that duct leakage meets the compliance criteria for sealed duct systems for which acceptance testing is required. Table NA7.5.3-1 summarizes the test procedures that shall be used to demonstrate compliance.

p.535Table NA7.5.3-1 – Duct Leakage Verification and Diagnostic Test Protocols

CaseUser and ApplicationProcedure(s)
Sealed and tested new duct systemsInstaller Testing ATT TestingNA7.5.3.2.3.2.1
Sealed and tested altered existing duct systemsInstaller Testing ATT TestingNA7.5.3.2.3.2.1
Sealed and tested altered existing duct systemsInstaller Testing and Inspection ATT Testing and VerificationNA7.5.3.2.3.2.2 NA7.5.3.2.3.2.3 NA7.5.3.2.3.2.4

p.535NA7.5.3.2.3.2.1 Diagnostic Duct Leakage from Fan Pressurization of Ducts

p.535The objective of this procedure is for an ATT to verify, the leakage of a new or altered duct system. The duct leakage shall be determined by pressurizing the entire duct system ducts to 25 Pa (0.1 inches water) with respect to outside. The following procedure shall be used for the fan pressurization tests:

p.535(a) Verify that the air handler, supply and return plenums and all the connectors, transition

p.535pieces, duct boots, and registers are installed, and ensure the following locations have been sealed:

p.5351. Connections to plenums and other connections to the air-handling unit.

p.5352. Refrigerant line and other penetrations into the air-handling unit.

p.5353. Air handler access door or panel (do not use permanent sealing material, metal tape is acceptable).

p.535The entire duct system including the air- handler shall be included in the test.

p.535Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processesp.536

p.5362025 Nonresidential Appendices (b) For newly installed or altered ducts, verify that cloth backed rubber adhesive duct

p.536tape has not been used.

p.536(c) Temporarily seal all the supply registers and return grilles, except for one large

p.536centrally located return grille or the air handler cabinet access door or panel. Verify that all outside air dampers and/or economizers are sealed prior to pressurizing the system.

p.536(d) Attach the fan flowmeter device to the duct system at the unsealed return grille or

p.536the air handler cabinet access door or panel.

p.536(e) Install a static pressure probe at a supply register located close to the air handler,

p.536or at the supply plenum.

p.536(f) Adjust the fan flowmeter to produce a positive 25 Pa (0.1 inches water) pressure at

p.536the supply register or the supply plenum with respect to the outside or with respect to the building space with the entry door open to the outside.

p.536(g) Record the flow through the flowmeter, this is the duct leakage flow at 25 Pa (0.1

p.536inches water).

p.536(h) Divide the duct leakage flow by the nominal air handler airflow determined by the

p.536procedure in Section NA7.5.3.2.3.1 and convert to a percentage. If the duct leakage flow percentage is equal to or less than the target compliance criterion from Table NA7.5.3-1, the system passes.