NA7.20.1.1 Air-Cooled and Adiabatic Gas Coolers and Gas Cooler Fan Motor Variable Speed Control

p.605NA7.20.1.1 Air-Cooled and Adiabatic Gas Coolers and Gas Cooler Fan Motor Variable Speed Control Conduct and document the following functional tests on all air-cooled and adiabatic gas coolers.

p.605NA7.20.1.1.1 Construction Inspection Prior to functional testing, verify and document the following:

p.605(a) Verify the control system minimum saturated condensing temperature (SCT)

p.605setpoint is at or below 60°F. If the design saturated suction temperature (SST) of the intermediate suction group is greater than or equal to 30°F, verify the control system SCT setpoint is at or below 70°F.

p.605(b) Verify accuracy of refrigerant pressure-temperature conversions and consistent

p.605use of either temperature or pressure for the controlled variable setpoint in the control system.

p.6051. The condensing temperature has an equivalent pressure during subcritical operation.

p.6052. Either pressure or temperature may be used in the control system as the controlled variable to maintain gas cooler pressure (condensing

p.605Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processesp.606

p.6062025 Nonresidential Appendices temperature) during subcritical operation, as long as the setpoint value is similarly expressed in pressure or temperature.

p.6063. Documentation may be achieved through pictures of control system screens or control system documentation, supported by sample calculations of observed pressures or temperatures and associated conversion values, as available in the control system interface.

p.606(c) Verify the gas cooler outlet temperature sensor reads accurately, using a NIST

p.606traceable instrument, including verification of at least two different gas cooler outlet readings. Calibrate if needed. Replace if outside manufacturer’s recommended calibration range. If multiple gas coolers are installed in parallel, ensure sensor is installed on the common header.

p.606(d) Verify the discharge pressure sensor (or gas cooler pressure if used) reads

p.606accurately, using a NIST traceable reference pressure gauge or meter, and with pressure checked for at least two pressures within the typical operating range. Calibrate if needed. Replace if outside manufacturers recommended calibration range.

p.606(e) Verify the ambient dry bulb temperature using a NIST traceable instrument,

p.606including verification of at least two different ambient readings. Calibrate if needed. Replace if outside manufacturer’s recommended calibration range. If the ambient dry bulb temperature sensor is installed between the adiabatic pad and the gas cooler coil for adiabatic gas coolers, verification must be performed when operating in “dry” mode.

p.606(f) Verify the ambient dry bulb temperature is not mounted in direct sunlight or is

p.606provided with a suitable solar shield.

p.606(g) Verify that all sensor readings used by the gas cooler controller display correct

p.606values at the controller, as well as derived values (e.g., observed pressure is correctly converted saturation temperature for CO2).

p.606(h) Verify that all fan motors are operational and rotating in the correct direction.

p.606(i) Verify that gas cooler fan speed controls are operational and controlling all gas

p.606cooler fan motors in unison.

p.606(j) Verify that all speed controls operate automatically in response to changes in

p.606pressure, gas cooler outlet temperature, and ambient dry bulb or precool air temperature.

p.606(k) Verify the installation of the gas cooler holdback valve, which may be located

p.606near the inlet of the intermediate pressure vessel or near the outlet of the gas cooler.

p.606Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processesp.607

p.6072025 Nonresidential Appendices NA7.20.1.1.2 Functional Testing (Option A: Subcritical Operation)