p.5182025 Nonresidential Appendices NA6.5.3 Enforcement Agency Responsibilities
p.518NA6.5.3.1 Plan Checker
p.518The enforcement agency plan checker or reviewer is responsible for ensuring that the plans identify all site-built fenestration and skylights occasionally residential site-built fenestration will be used and identified on the Fenestration Certificate of Compliance form. The plan checker shall ensure that site-built fenestration and skylights using the alternate default procedure shall meet the following:
p.518(a) Confirm that U-factors, SHGC and VT (for Commercial use only) values are clearly
p.518shown on the window schedules on the plans and documented on the energy compliance forms, and
p.518(b) Confirm that manufacturer documentation of the Glazing Type and Frame Type
p.518has been provided for the each of the fenestration products using the procedure of this appendix and documents the Center of Glass values; and
p.518(c) Verify the building meets the non-certified fenestration requirement
p.518(Nonresidential: up to 200 ft2 of skylight area, or an altered vertical fenestration; Residential: up to 250 ft2 in area, or 0.5% of the CFA, whichever is greater); and
p.518(d) For Nonresidential, confirm that a Fenestration Certificate of Compliance Label
p.518Certificate has been completed for each non-rated site-built fenestration product, or for Residential, verify that the non-rated site-built fenestration efficiencies match the building plans and energy compliance forms.
p.518NA6.5.3.2 Enforcement Agency Inspector
p.518(a) For Residential up to 250 ft2 in area or 0.5% of the CFA, whichever is greater, of
p.518non-rated site-built fenestration is allowed. The inspector should verify the manufacturer’s label attached to each residential site-built fenestration product to ensure that it matches with residential energy compliance forms. (b) For Nonresidential up to 200 ft2 of skylight area and altered vertical site-built
p.518fenestration are allowed for this alternative procedure. The field inspector is responsible for ensuring that the U-factor, SHGC and VT for the installed fenestration match the building plans and energy compliance forms. Inspection of the Commission’s Fenestration Certificate of Compliance Label Certificate shall match each of the Prescriptive Certificate of Compliance form or the Performance Certificate of Compliance forms for the installed site-built fenestration product.
p.518Appendix NA6– Alternate Default Fenestration Procedure to Calculate Thermal Performance