NA2.2.3.3 Traditional Flow Capture Hood

p.492NA2.2.3.3 Traditional Flow Capture Hood

p.492A traditional flow capture hood1F2 meeting the applicable instrumentation specifications in Section NA2.2.2.2 may be used to verify the ventilation system airflow rate if the non- powered flow hood has a capture area at least as large as the ventilation system inlet or outlet terminal, register or grille in all dimensions.

p.492NA2.2.4 Procedures

p.492This section describes the procedures used to verify Mechanical ventilation system airflow.

p.492NA2.2.4.1 Mechanical Ventilation Airflow Rate Measurement - Continuous Operation

p.492If multiple fans are specified to operate simultaneously to provide the total required ventilation airflow, the measurements shall be made with all applicable fans operating simultaneously.

p.492NA2.2.4.1.1 Supply and Exhaust Ventilation Systems

p.492a) A flow measuring device that meets the applicable instrumentation requirements

p.492specified in Section NA2.2.3.2, and NA2.2.3.3 shall be used to measure the ventilation airflow(s).

p.492b) Measure and record the ventilation airflow(s).

p.492c) If the measured total airflow is greater than or equal to the ventilation airflow rate

p.492required by the Standards or the Certificate of Compliance, the mechanical ventilation system complies. Otherwise the mechanical ventilation system does not comply, and corrective action shall be taken.

p.492NA2.2.4.1.2 Balanced Ventilation Systems

p.492a) A flow measuring device that meets the applicable instrumentation requirements

p.492given in Section NA2.2.3.2 and NA2.2.3.3 shall be used to measure the ventilation airflows.

p.4922 Also known as “non-powered flow hood, "standard" flow hood, "commercially available" flow hood, or "passive" flow hood.

p.492Appendix NA2 – Nonresidential Field Verification and Diagnostic Test Proceduresp.493

p.4932025 Nonresidential Appendices b) Confirm that both the supply side and the exhaust side of the balanced system

p.493operate simultaneously in response to a shared system control.

p.493c) Measure the airflow rate for the exhaust side of the system.

p.493d) Measure the airflow rate for the supply side of the system.

p.493e) Calculate the percent difference between the exhaust and supply airflow rates.

p.493f) Calculate the average of the exhaust and the supply airflow rates.

p.493g) If the exhaust and supply airflow rates are within 20% of each other, and the average

p.493of the exhaust and supply airflow rates is greater than or equal to the airflow rate required by the Standards or the Certificate of Compliance, the balanced ventilation system complies. Otherwise, the system does not comply, and corrective action shall be taken.

p.493h) If the balanced system is an HRV or ERV and compliance with a recovery efficiency

p.493or fan efficacy specification is required, then also perform the verification specified in NA2.2.4.1.5.