NA1.6.4 Procedures - Re-sampling, Full Testing and Corrective Action

p.480NA1.6.4 Procedures - Re-sampling, Full Testing and Corrective Action

p.480“Re-sampling” refers to the procedure that requires testing of additional systems or dwelling units within a group when the selected sample from a group fails to comply with the verification requirements.

p.480When a failure is encountered during sample testing, the failure shall be entered into the Provider’s Data Registry. Corrective action shall be taken on the failed system and then retested to verify that corrective action was successful. Corrective action and retesting on the system shall be repeated until the testing indicates compliance and the results have been entered into the Data Registry, whereupon a registered Certificate of Verification for the system shall be made available to the ECC-Rater, the builder, the enforcement agency, and other authorized users of the Data Registry.

p.480In addition, the ECC-Rater shall conduct re-sampling to assess whether the first failure in the group is unique or if the rest of the units in the group are likely to have similar failings.

p.480NA1.6.4.1 Re-sampling procedures for a “closed” group

p.480The ECC-Rater shall randomly select for re-sampling one of the remaining untested systems or dwelling units in the group for testing.

p.480If testing in the re-sample confirms that the requirements for compliance credit are met, then the system or dwelling unit with the failure shall not be considered an indication of failure in the other units in the group. The ECC-Rater shall transmit the re-sample test results to the Data Registry, whereupon the Provider shall make available to the ECC-Rater, the builder, the enforcement agency, and other authorized users of the Data Registry, a copy of the registered Certificate of Verification for each of the remaining units in the group including the dwelling unit in the re-sample.

p.480If field verification and diagnostic testing of the second sample results in a failure, the ECC- Rater shall report the second failure to the ECC-Provider, the builder, and the enforcement agency. All systems or dwelling units in the group must thereafter be individually field verified and diagnostically tested.

p.480NA1.6.4.2 Corrective Action

p.480The builder shall take corrective action on any system or dwelling unit in the group that failed to comply when tested. In cases where corrective action would require destruction of building components, and the performance compliance method is used, the builder may

p.480Appendix NA1– Nonresidential Verification, Testing, and Documentation Proceduresp.481

p.4812025 Nonresidential Appendices choose to reanalyze compliance and choose different measures that will achieve compliance. In this case a new Certificate of Compliance shall be completed and submitted to the ECC-Provider, the ECC-Rater, and the enforcement agency. The ECC-Rater shall conduct field verification and diagnostic testing for each of these measures to verify that problems have been corrected and that the requirements for compliance have been met. Upon verification of compliance, the ECC-Rater shall enter the test results into the Data Registry. Whereupon the Provider shall make available to the ECC-Rater, the builder, the enforcement agency, and other authorized users of the Data Registry a copy of the registered Certificate of Verification for each individual unit in the group.

p.481The ECC-Provider shall file a report with the enforcement agency explaining all action taken (including field verification, diagnostic testing, and corrective action,) to bring into compliance systems or dwelling units for which full testing has been required. If corrective action requires work not specifically exempted by the CMC or the CBC, the builder shall obtain a permit from the enforcement agency prior to commencement of any of the work.

p.481Corrections to avoid reporting a failure to the Data Registry shall not be made to a sampled or re-sampled feature after the ECC-Rater selects the sample feature, or during the course of testing of the unit. If it becomes evident that such corrections have been made to a sampled or re-sampled feature to avoid reporting a failure, field verification and diagnostic testing shall be required to be performed on 100 percent of the individual systems or dwelling units in the group.