JA15.2.3 Ventilation Requirements

p.2762025 Joint Appendices

p.276JA15.2.3 Ventilation Requirements

p.276The reserved pathway and penetrations through the building envelope shall meet the following requirements:

p.276(a) If the input capacity of the gas water heating system is less than 200,000 Btu

p.276per hour, the minimum air flow rate shall be 70 CFM per 10,000 Btu per hour input of the gas or propane water heating system and the total external static pressure drop of ductwork and louvers shall not exceed 0.17 inches water column when the future heat pump water heater is installed.

p.276(b) If the input capacity of the gas water heating system is greater than or equal to

p.276200,000 Btu per hour, the minimum air flow rate shall be 420 CFM per 10,000 Btu per hour input of the gas or propane water heating system and the total external static pressure drop of ductwork and louvers shall not exceed 0.17 inches water column when the future heat pump water heater is installed.

p.276JA15.2.4 Condensate Drainage Piping Requirements The condensate drainage piping shall meet the following requirements:

p.276(a) If the input capacity of the gas water heating system is less than 200,000 Btu

p.276per hour, condensate drainage shall be sized for 0.2 tons of refrigeration capacity per 10,000 Btu per hour input.

p.276(b) If the input capacity of the gas water heating system is greater than or equal to

p.276200,000 Btu per hour, condensate drainage shall be sized for 0.7 tons of refrigeration capacity per 10,000 Btu per hour input.

p.276JA15.2.5 Electrical Requirements

p.276The electrical system serving the heat pump shall meet the following requirements:

p.276(a) If the input capacity of the gas water heating system is less than 200,000 Btu

p.276per hour, provide 0.1 kVA per 10,000 Btu per hour input.

p.276(b) If the input capacity of the gas water heating system is greater than or equal to

p.276200,000 Btu per hour, provide 1.1 kVA per 10,000 Btu per hour input.

p.276The electrical system serving the temperature maintenance tank shall meet the following requirements:

p.276(c) If the input capacity of the gas water heating system is less than 200,000 Btu

p.276per hour, provide 1.0 kVA per 10,000 Btu per hour input.

p.276(d) If the input capacity of the gas water heating system is greater than or equal to

p.276200,000 Btu per hour, provide 0.6 kVA per 10,000 Btu per hour input.

p.276Appendix JA15 – Qualification Requirements for Central Heat Pump Water Heater Ready