p.449RA4.3.2 Evaporative Cooling
p.449Qualifying equipment is limited to either indirect-direct or indirect evaporative coolers. Direct evaporative coolers and indirect or indirect-direct evaporative coolers that do not meet the following eligibility criteria shall not be used.
p.449RA4.3.2.1 Eligibility Testing
p.449The installing contractor shall complete the following eligibility testing and document the results on the applicable Certificate of Installation.
p.449(a) Eligible equipment shall be listed under Title 20 Appliance Standards.
p.449– Eligibility Criteria for Energy Efficiency Measuresp.450
p.4502025 Residential Appendices (b) The equipment manufacturer shall certify to the Commission that water use does not
p.450exceed 7.5 gallons per ton hour based on the Title 20 Appliance Standards testing criteria.
p.450(c) Equipment shall be permanently installed (no window or portable units).
p.450(d) Installation shall provide for automatic relief of supply air from the house with maximum
p.450air velocity through the relief dampers not exceeding 800 fpm (at the Title 20 rated airflow). Pressure relief dampers and ductwork shall be distributed to provide adequate airflow through all habitable rooms. For installations with an attic, ceiling dampers shall be installed to relieve air into the attic, and then to outside through attic vents. For installations without an attic, sidewall relief dampers are acceptable.
p.450(e) To minimize water consumption, bleed systems shall not be allowed.
p.450(f) A water quality management system (either “pump out” or conductivity sensor) is
p.450required. “Pump out” systems can either be integral to the evaporative cooler or they can be accessories that operate on a timed interval. The time interval between dumps shall be set to a minimum of six hours of cooler operation. Longer intervals are encouraged if local water quality allows.