NA2.2.2 Instrumentation Specifications

Table NA2.2-1 –Summary of Verification and Diagnosticprocedures
DiagnosticDescriptionProcedure
Dwelling-Unit Mechanical Ventilation AirflowVerification of the dwelling unit ventilation system airflow rate. Continuous OperationNA2.2.4.1
Dwelling-Unit Mechanical Ventilation AirflowVerification of the dwelling unit ventilation system airflow rate. Intermittent OperationNA2.2.4.1.3
Kitchen Local Mechanical Exhaust VerificationVerification of vented range hood airflow rate or capture efficiencyNA2.2.4.1.4
Heat Recovery Ventilation (HRV) or Energy Recovery Ventilation (ERV) Rated Performance VerificationVerification of the HRV/ERV fan efficacy (W/cfm) or heat recovery efficiency.NA2.2.4.1.5

p.490NA2.2.2 Instrumentation Specifications

p.490The instrumentation for the air distribution diagnostic measurements shall conform to the following specifications:

p.490NA2.2.2.1 Pressure Measurements

p.490All pressure measurements shall be measured with measurement systems (i.e., sensor plus data acquisition system) having an accuracy equal to or better than ± 1% of pressure reading or ± 0.2 Pa (0.0008 inches water) (whichever is greater). All pressure measurements within the duct system shall be made with static pressure probes such as Dwyer A303 or equivalent.

p.490NA2.2.2.2 Airflow Rate Measurements

p.490All measurements of ventilation fan airflow rate shall be made with an airflow rate measurement apparatus (i.e., sensor plus data acquisition system) having an accuracy equal to or better than ± 10% of reading. The apparatus shall have an accuracy specification that is applicable to the airflow rates that must be verified utilizing the procedures in Section NA2.2.4.

p.490NA2.2.2.3 Calibration

p.490All instrumentation used for mechanical ventilation system airflow rate diagnostic measurements shall be calibrated according to the manufacturer’s calibration procedure to ensure the airflow measurement apparatus conforms to the accuracy requirement specified in Section NA2.2.2.2.

p.490Appendix NA2 – Nonresidential Field Verification and Diagnostic Test Proceduresp.491

p.4912025 Nonresidential Appendices NA2.2.3 Diagnostic Apparatus for Measurement of Ventilation System Airflow