(d) Sign lighting controls. All sign lighting shall meet the requirements below as applicable: (includes (d)–(e))

p.532(d) Sign lighting controls. All sign lighting shall meet the requirements below as applicable:

p.5321. Indoor signs. All indoor sign lighting other than exit sign lighting shall be controlled with an automatic time-switch control or astronomical time-switch control.

p.5322. Outdoor signs. Outdoor sign lighting shall meet the following requirements as applicable:

p.532A. All outdoor sign lighting shall be controlled with a photocontrol in addition to an automatic

p.532time-switch control, or an astronomical time-switch control.

p.532B. All outdoor sign lighting that is ON both day and night shall be controlled with a dimmer

p.532that provides the ability to automatically reduce sign lighting power by a minimum of 65 percent during nighttime hours. Signs that are illuminated at night and for more than 1 hour during daylight hours shall be considered ON both day and night.

p.5323. Demand Responsive Electronic Message Center (EMC) control. See Section 110.12 for requirements for demand responsive EMC controls.p.533

p.532SECTION 160.5 – MANDATORY LIGHTING REQUIREMENTS FOR INDOOR AND OUTDOOR SPACES

p.533(e) Lighting control acceptance and installation certificate requirement. Multifamily common use

p.533areas shall comply with the applicable requirements of Sections 160.5(e)1 through 160.5(e)3.

p.5331. Lighting control acceptance requirements. Before an occupancy permit is granted, indoor and outdoor lighting controls serving the building, area or site and installed to comply with Section 160.5(b)4D, 160.5(b)4C, 160.5(b)4E, 160.5(c)2 or 170.2(e)1Aiij shall be certified as meeting the Acceptance Requirements for Code Compliance as specified by Reference Nonresidential Appendix NA7.6 and NA7.8. A Certificate of Acceptance shall be submitted to the enforcement agency under Section 10-103(a) of Part 1 that the equipment and systems meet the acceptance requirements:

p.533A. Reserved;

p.533B. Reserved;

p.533C. Daylight responsive controls shall be tested in accordance with Reference Nonresidential

p.533Appendix NA7.6.1;

p.533D. Lighting shut-OFF controls shall be tested in accordance with Reference Nonresidential

p.533Appendix NA7.6.2;

p.533E. Demand responsive lighting controls shall be tested in accordance with Reference

p.533Nonresidential Appendix NA7.6.3; and

p.533F. Outdoor lighting controls shall be tested in accordance with Reference Nonresidential

p.533Appendix NA7.8; and

p.533G. Lighting systems receiving the Institutional Tuning Power Adjustment Factor shall be tested

p.533in accordance with Reference Nonresidential Appendix NA7.6.4. H. Demand responsive controls required to control controlled receptacles shall be tested in

p.533accordance with Reference Nonresidential Appendix NA7.6.5.

p.5332. Lighting control installation certificate requirements. To be recognized for compliance with Part 6, an Installation Certificate shall be submitted in accordance with Section 10-103(a) for any lighting control system, energy management control system, interlocked lighting system, lighting power adjustment factor, or additional wattage available for a videoconference studio, in accordance with the following requirements, as applicable:

p.533A. Certification that when a lighting control system is installed to comply with lighting control

p.533requirements in Part 6, it complies with the applicable requirements of Section 110.9 and complies with Reference Nonresidential Appendix NA7.7.1.

p.533B. Certification that when an energy management control system is installed to function as a

p.533lighting control required by Part 6, it functionally meets all applicable requirements for each application for which it is installed, in accordance with Sections 110.9, 160, 170 and 180, and complies with Reference Nonresidential Appendix NA7.7.2.

p.533C. Certification that interlocked lighting systems used to serve an approved area comply with

p.533Section 170.2(e)2A and comply with Reference Nonresidential Appendix NA7.7.4.p.534

p.533SECTION 160.5 – MANDATORY LIGHTING REQUIREMENTS FOR INDOOR AND OUTDOOR SPACES

Scanned crop of table from PDF page 534
Text in this table

SECTION 160.5 – MANDATORY LIGHTING REQUIREMENTS FOR INDOOR AND OUTDOOR SPACES D. Certification that lighting controls installed to earn a lighting Power Adjustment Factor (PAF) comply with Section 170.2(e)2B and comply with Reference Nonresidential Appendix NA7.7.5. E. Reserved. 3. When certification is required by Title 24, Part 1, Section 10-103.1, the acceptance testing specified by Section 160.5(e) shall be performed by a Certified Lighting Controls Acceptance Test Technician (CLCATT). If the CLCATT is operating as an employee, the CLCATT shall be employed by a Certified Lighting Controls Acceptance Test Employer. The CLCATT shall disclose on the Certificate of Acceptance a valid CLCATT certification identification number issued by an approved Acceptance Test Technician Certification Provider. The CLCATT shall complete all Certificate of Acceptance documentation in accordance with the applicable requirements in Section 10-103(a)4. NOTE: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code. Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5, 25402.8, and 25943, Public Resources Code.