| Building Walls, Component Floors, Doors, Fenestrations, and QII | CZ 1 | CZ 2 | CZ 3 | CZ 4 | CZ 5 | CZ 6 | CZ 7 | CZ 8 | CZ 9 | CZ 10 | CZ 11 | CZ 12 | CZ 13 | CZ 14 | CZ 15 | CZ 16 | ||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Above | Grade Framed Walls3 | U 0.048 | U 0.048 | U 0.048 | U 0.048 | U 0.048 | U 0.065 | U 0.065 | U 0.048 | U 0.048 | U 0.048 | U 0.048 | U 0.048 | U 0.048 | U 0.048 | U 0.048 | U 0.048 | |
| Above Mass | Grade Masonry/ Wall Interior4,5,6 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.059 R 17 | |
| Above Mass | Grade Masonry/ Wall Exterior4,5,6 | U 0.125 R 8.0 | U 0.125 R 8.0 | U 0.125 R 8.0 | U 0.125 R 8.0 | U 0.125 R 8.0 | U 0.125 R 8.0 | U 0.125 R 8.0 | U 0.125 R 8.0 | U 0.125 R 8.0 | U 0.125 R 8.0 | U 0.125 R 8.0 | U 0.125 R 8.0 | U 0.125 R 8.0 | U 0.125 R 8.0 | U 0.125 R 8.0 | U 0.077 R 13 | |
| Below | Grade Interior Walls7 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.077 R 13 | U 0.067 R 15 | |
| Below | Grade ExteriorWalls 7 | U 0.200 R 5.0 | U 0.200 R 5.0 | U 0.200 R 5.0 | U 0.200 R 5.0 | U 0.200 R 5.0 | U 0.200 R 5.0 | U 0.200 R 5.0 | U 0.200 R 5.0 | U 0.200 R 5.0 | U 0.200 R 5.0 | U 0.200 R 5.0 | U 0.200 R 5.0 | U 0.200 R 5.0 | U 0.100 R 10 | U 0.100 R 10 | U 0.053 R 19 | |
| Slab | Perimeter Floors | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | F-0.58 R 7.0 | |
| Raised | Floors | U 0.037 R 19 | U 0.037 R 19 | U 0.037 R 19 | U 0.037 R 19 | U 0.037 R 19 | U 0.037 R 19 | U 0.037 R 19 | U 0.037 R 19 | U 0.037 R 19 | U 0.037 R 19 | U 0.037 R 19 | U 0.037 R 19 | U 0.037 R 19 | U 0.037 R 19 | U 0.037 R 19 | U 0.037 R 19 | |
| Concrete | Raised Floors | U 0.092 R 8.0 | U 0.092 R 8.0 | U 0.269 R 0 | U 0.269 R 0 | U .269 R 0 | U 0.269 R 0 | U 0.269 R 0 | U 0.269 R 0 | U 0.269 R 0 | U 0.269 R 0 | U 0.092 R 8.0 | U 0.138 R 4.0 | U 0.092 R 8.0 | U 0.092 R 8.0 | U 0.138 R 4.0 | U 0.092 R 8.0 | |
| factor Fenestration - Maximum U- 12 | 0.27 | 0.27 | 0.27 | 0.27 | 0.27 | 0.30 | 0.30 | 0.30 | 0.30 | 0.30 | 0.27 | 0.27 | 0.27 | 0.27 | 0.30 | 0.27 | ||
| SHGC Fenestration - Maximum | NR | 0.23 | NR | 0.23 | NR | 0.23 | 0.23 | 0.23 | 0.23 | 0.23 | 0.23 | 0.23 | 0.23 | 0.23 | 0.20 | NR | ||
| Total Fenestration - Maximum Area | 20% | 20% | 20% | 20% | 20% | 20% | 20% | 20% | 20% | 20% | 20% | 20% | 20% | 20% | 20% | 20% | ||
| West Fenestration - Maximum Facing Area | NR | 5% | NR | 5% | NR | 5% | 5% | 5% | 5% | 5% | 5% | 5% | 5% | 5% | 5% | NR | ||
| Door | - Maximum U-Factor | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | |
| Quality Installation | Insulation | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |
| Building HVAC | Envelope and Water Heating Systems | CZ 1 | CZ 2 | CZ 3 | CZ 4 | CZ 5 | CZ 6 | CZ 7 | CZ 8 | CZ 9 | CZ 10 | CZ 11 | CZ 12 | CZ 13 | CZ 14 | CZ 15 | CZ 16 | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Space Allowed | Heating - Electric Resistance | No | No | No | No | No | No | No | No | No | No | No | No | No | No | No | No | |
| Space | Heating - If gas, AFUE10 | NA | NA | NA | NA | NA | NA | NA | NA | NA | NA | NA | NA | NA | NA | NA | NA | |
| Space | Heating - If Heat Pump, HSPF28 | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | |
| Space | Cooling -SEER2 | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | |
| Space | Cooling - Whole-House Fan9 | NR | NR | NR | NR | NR | NR | NR | REQ | REQ | REQ | REQ | REQ | REQ | REQ | NR | NR | |
| Refrigerant Air Charge Verification Conditioners | NR | REQ | NR | NR | NR | NR | NR | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | NR | ||
| Refrigerant Heat Charge Verification Pumps | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | ||
| Central System | Fan Integrated Ventilation - Fan Efficacy | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | |
| Option Roof/Ceiling | B13 - Duct Insulation | R 8 | R 8 | R 6 | R 8 | R 6 | R 6 | R 6 | R 8 | R 8 | R 8 | R 8 | R 8 | R 8 | R 8 | R 8 | R 8 | |
| Option | B13 - §150.1(c) 9A | NA | NA | NA | NA | NA | NA | NA | NA | NA | NA | NA | NA | NA | NA | NA | NA | |
| Option Roof/Ceiling | C14 - Duct Insulation | R 6 | R 6 | R 6 | R 6 | R 6 | R 6 | R 6 | R 6 | R 6 | R 6 | R 6 | R 6 | R 6 | R 6 | R 6 | R 6 | |
| Option | C11,14 - §150.1(c) 9B | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | |
| FID Installed required if HRV/ERV Systems - §150.1(c) 15 | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | ||
| Water | Heating - §150.1(c) 8 | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | |
| Footnote | requirements to TABLE | 150.1-A: |
p.449TABLE 150.1-B RESERVED
p.448Install the specified R-value with an air space present between the roofing and the roof deck, such as standard installation of concrete or clay tile. R-values shown for below roof deck insulation are for wood-framed construction with insulation installed between the framing members. Alternatives including insulation above rafters or above roof deck shall comply with the performance standards. Assembly U-factors for exterior framed walls can be met with cavity insulation alone or with continuous insulation alone, or with both cavity and continuous insulation that results in an assembly U- factor equal to or less than the U-factor shown. Use Reference Joint Appendices JA4 Table 4.3.1, 4.3.1(a), or Table 4.3.4 to determine alternative insulation products to be less than or equal to the required Assembly U-factors for roofs can be met with cavity insulation alone or with continuous insulation alone, or with both cavity and continuous insulation that results in an assembly U-factor equal to or less than the U-factor shown. Use Reference Joint Appendices JA4 Table 4.2.2 to determine alternative insulation products to be less than or equal to the required maximum U-factor. R-values shown represent the required insulation to meet the maximum U-factor with cavity insulation alone. Mass wall has a heat capacity greater than or equal to 7.0 Btu/h-ft2. “Interior” denotes insulation installed on the inside surface of the wall. “Exterior” denotes insulation installed on the exterior surface of the wall. Below grade “interior” denotes insulation installed on the inside surface of the wall, and below grade “exterior” denotes insulation installed on the outside surface of the wall. HSPF2 means heating seasonal performance factor. When whole-house fans are required (REQ), only those whole-house fans that are listed in the Home Ventilating Institute Certified Products Directory may be installed. Compliance requires installation of one or more WHFs whose total airflow cfm is capable of meeting or exceeding a minimum 1.5 cfm/ square foot of conditioned floor area as specified by Section 150.1(c)12. A supplemental heating unit may be installed in a space served directly or indirectly by a primary heating system, provided that the unit thermal capacity does not exceed 2 kilowatts or 7,000 Btu/hr and is controlled by a time-limiting device not exceeding 30 minutes. For duct and air handler location: REQ denotes location in conditioned space. When the table indicates ducts and air handlers are in conditioned space, a verification is required as specified by Reference Residential Appendix RA3.1.4.3.8. New dwelling units with a conditioned floor area of 500 square feet or less in Climate Zone 5 may comply with a maximum U-factor of 0.30. Option B meets §150.1(c)9A Option C meets §150.1(c)9Bp.449
| Climate Zone | A - CFA | B - Dwelling Units |
|---|---|---|
| 1 | 0.793 | 1.27 |
| 2 | 0.621 | 1.22 |
| 3 | 0.628 | 1.12 |
| 4 | 0.586 | 1.21 |
| 5 | 0.585 | 1.06 |
| 6 | 0.594 | 1.23 |
| 7 | 0.572 | 1.15 |
| 8 | 0.586 | 1.37 |
| 9 | 0.613 | 1.36 |
| 10 | 0.627 | 1.41 |
| 11 | 0.836 | 1.44 |
| 12 | 0.613 | 1.40 |
| 13 | 0.894 | 1.51 |
| 14 | 0.741 | 1.26 |
| 15 | 1.56 | 1.47 |
| 16 | 0.59 | 1.22 |
p.446SECTION 150.1 – PERFORMANCE AND PRESCRIPTIVE COMPLIANCE APPROACHES FOR SINGLE- FAMILY RESIDENTIAL BUILDINGSp.447
p.447SECTION 150.1 – PERFORMANCE AND PRESCRIPTIVE COMPLIANCE APPROACHES FOR SINGLE- FAMILY RESIDENTIAL BUILDINGSp.448
p.448SECTION 150.1 – PERFORMANCE AND PRESCRIPTIVE COMPLIANCE APPROACHES FOR SINGLE- FAMILY RESIDENTIAL BUILDINGS
p.449SECTION 150.1 – PERFORMANCE AND PRESCRIPTIVE COMPLIANCE APPROACHES FOR SINGLE- FAMILY RESIDENTIAL BUILDINGS