SECTION 150.1 – PERFORMANCE AND PRESCRIPTIVE COMPLIANCE APPROACHES FOR SINGLE-FAMILY RESIDENTIAL BUILDINGS (part 2 of 2)

p.4462025 Building Energy Efficiency Standards

p.4472025 Building Energy Efficiency Standards

TABLE 150.1-A COMPONENT PACKAGE – Single-Family Standard Building Design (continued) p.446 Download CSV
Building Walls, Component Floors, Doors, Fenestrations, and QIICZ 1CZ 2CZ 3CZ 4CZ 5CZ 6CZ 7CZ 8CZ 9CZ 10CZ 11CZ 12CZ 13CZ 14CZ 15CZ 16
AboveGrade Framed Walls3U 0.048U 0.048U 0.048U 0.048U 0.048U 0.065U 0.065U 0.048U 0.048U 0.048U 0.048U 0.048U 0.048U 0.048U 0.048U 0.048
Above MassGrade Masonry/ Wall Interior4,5,6U 0.077 R 13U 0.077 R 13U 0.077 R 13U 0.077 R 13U 0.077 R 13U 0.077 R 13U 0.077 R 13U 0.077 R 13U 0.077 R 13U 0.077 R 13U 0.077 R 13U 0.077 R 13U 0.077 R 13U 0.077 R 13U 0.077 R 13U 0.059 R 17
Above MassGrade Masonry/ Wall Exterior4,5,6U 0.125 R 8.0U 0.125 R 8.0U 0.125 R 8.0U 0.125 R 8.0U 0.125 R 8.0U 0.125 R 8.0U 0.125 R 8.0U 0.125 R 8.0U 0.125 R 8.0U 0.125 R 8.0U 0.125 R 8.0U 0.125 R 8.0U 0.125 R 8.0U 0.125 R 8.0U 0.125 R 8.0U 0.077 R 13
BelowGrade Interior Walls7U 0.077 R 13U 0.077 R 13U 0.077 R 13U 0.077 R 13U 0.077 R 13U 0.077 R 13U 0.077 R 13U 0.077 R 13U 0.077 R 13U 0.077 R 13U 0.077 R 13U 0.077 R 13U 0.077 R 13U 0.077 R 13U 0.077 R 13U 0.067 R 15
BelowGrade ExteriorWalls 7U 0.200 R 5.0U 0.200 R 5.0U 0.200 R 5.0U 0.200 R 5.0U 0.200 R 5.0U 0.200 R 5.0U 0.200 R 5.0U 0.200 R 5.0U 0.200 R 5.0U 0.200 R 5.0U 0.200 R 5.0U 0.200 R 5.0U 0.200 R 5.0U 0.100 R 10U 0.100 R 10U 0.053 R 19
SlabPerimeter FloorsNRNRNRNRNRNRNRNRNRNRNRNRNRNRNRF-0.58 R 7.0
RaisedFloorsU 0.037 R 19U 0.037 R 19U 0.037 R 19U 0.037 R 19U 0.037 R 19U 0.037 R 19U 0.037 R 19U 0.037 R 19U 0.037 R 19U 0.037 R 19U 0.037 R 19U 0.037 R 19U 0.037 R 19U 0.037 R 19U 0.037 R 19U 0.037 R 19
ConcreteRaised FloorsU 0.092 R 8.0U 0.092 R 8.0U 0.269 R 0U 0.269 R 0U .269 R 0U 0.269 R 0U 0.269 R 0U 0.269 R 0U 0.269 R 0U 0.269 R 0U 0.092 R 8.0U 0.138 R 4.0U 0.092 R 8.0U 0.092 R 8.0U 0.138 R 4.0U 0.092 R 8.0
factor Fenestration - Maximum U- 120.270.270.270.270.270.300.300.300.300.300.270.270.270.270.300.27
SHGC Fenestration - MaximumNR0.23NR0.23NR0.230.230.230.230.230.230.230.230.230.20NR
Total Fenestration - Maximum Area20%20%20%20%20%20%20%20%20%20%20%20%20%20%20%20%
West Fenestration - Maximum Facing AreaNR5%NR5%NR5%5%5%5%5%5%5%5%5%5%NR
Door- Maximum U-Factor0.200.200.200.200.200.200.200.200.200.200.200.200.200.200.200.20
Quality InstallationInsulationYesYesYesYesYesYesYesYesYesYesYesYesYesYesYesYes
TABLE 150.1-A COMPONENT PACKAGE – Single- Family Standard Building Design (continued) p.447 Download CSV
Building HVACEnvelope and Water Heating SystemsCZ 1CZ 2CZ 3CZ 4CZ 5CZ 6CZ 7CZ 8CZ 9CZ 10CZ 11CZ 12CZ 13CZ 14CZ 15CZ 16
Space AllowedHeating - Electric ResistanceNoNoNoNoNoNoNoNoNoNoNoNoNoNoNoNo
SpaceHeating - If gas, AFUE10NANANANANANANANANANANANANANANANA
SpaceHeating - If Heat Pump, HSPF28MINMINMINMINMINMINMINMINMINMINMINMINMINMINMINMIN
SpaceCooling -SEER2MINMINMINMINMINMINMINMINMINMINMINMINMINMINMINMIN
SpaceCooling - Whole-House Fan9NRNRNRNRNRNRNRREQREQREQREQREQREQREQNRNR
Refrigerant Air Charge Verification ConditionersNRREQNRNRNRNRNRREQREQREQREQREQREQREQREQNR
Refrigerant Heat Charge Verification PumpsREQREQREQREQREQREQREQREQREQREQREQREQREQREQREQREQ
Central SystemFan Integrated Ventilation - Fan EfficacyREQREQREQREQREQREQREQREQREQREQREQREQREQREQREQREQ
Option Roof/CeilingB13 - Duct InsulationR 8R 8R 6R 8R 6R 6R 6R 8R 8R 8R 8R 8R 8R 8R 8R 8
OptionB13 - §150.1(c) 9ANANANANANANANANANANANANANANANANA
Option Roof/CeilingC14 - Duct InsulationR 6R 6R 6R 6R 6R 6R 6R 6R 6R 6R 6R 6R 6R 6R 6R 6
OptionC11,14 - §150.1(c) 9BREQREQREQREQREQREQREQREQREQREQREQREQREQREQREQREQ
FID Installed required if HRV/ERV Systems - §150.1(c) 15REQREQREQREQREQREQREQREQREQREQREQREQREQREQREQREQ
WaterHeating - §150.1(c) 8REQREQREQREQREQREQREQREQREQREQREQREQREQREQREQREQ
Footnoterequirements to TABLE150.1-A:

p.449TABLE 150.1-B RESERVED

p.448Install the specified R-value with an air space present between the roofing and the roof deck, such as standard installation of concrete or clay tile. R-values shown for below roof deck insulation are for wood-framed construction with insulation installed between the framing members. Alternatives including insulation above rafters or above roof deck shall comply with the performance standards. Assembly U-factors for exterior framed walls can be met with cavity insulation alone or with continuous insulation alone, or with both cavity and continuous insulation that results in an assembly U- factor equal to or less than the U-factor shown. Use Reference Joint Appendices JA4 Table 4.3.1, 4.3.1(a), or Table 4.3.4 to determine alternative insulation products to be less than or equal to the required Assembly U-factors for roofs can be met with cavity insulation alone or with continuous insulation alone, or with both cavity and continuous insulation that results in an assembly U-factor equal to or less than the U-factor shown. Use Reference Joint Appendices JA4 Table 4.2.2 to determine alternative insulation products to be less than or equal to the required maximum U-factor. R-values shown represent the required insulation to meet the maximum U-factor with cavity insulation alone. Mass wall has a heat capacity greater than or equal to 7.0 Btu/h-ft2. “Interior” denotes insulation installed on the inside surface of the wall. “Exterior” denotes insulation installed on the exterior surface of the wall. Below grade “interior” denotes insulation installed on the inside surface of the wall, and below grade “exterior” denotes insulation installed on the outside surface of the wall. HSPF2 means heating seasonal performance factor. When whole-house fans are required (REQ), only those whole-house fans that are listed in the Home Ventilating Institute Certified Products Directory may be installed. Compliance requires installation of one or more WHFs whose total airflow cfm is capable of meeting or exceeding a minimum 1.5 cfm/ square foot of conditioned floor area as specified by Section 150.1(c)12. A supplemental heating unit may be installed in a space served directly or indirectly by a primary heating system, provided that the unit thermal capacity does not exceed 2 kilowatts or 7,000 Btu/hr and is controlled by a time-limiting device not exceeding 30 minutes. For duct and air handler location: REQ denotes location in conditioned space. When the table indicates ducts and air handlers are in conditioned space, a verification is required as specified by Reference Residential Appendix RA3.1.4.3.8. New dwelling units with a conditioned floor area of 500 square feet or less in Climate Zone 5 may comply with a maximum U-factor of 0.30. Option B meets §150.1(c)9A Option C meets §150.1(c)9Bp.449

Table 150.1-C – CFA and Dwelling Unit Adjustment Factors p.449 Download CSV
Climate ZoneA - CFAB - Dwelling Units
10.7931.27
20.6211.22
30.6281.12
40.5861.21
50.5851.06
60.5941.23
70.5721.15
80.5861.37
90.6131.36
100.6271.41
110.8361.44
120.6131.40
130.8941.51
140.7411.26
151.561.47
160.591.22

p.446SECTION 150.1 – PERFORMANCE AND PRESCRIPTIVE COMPLIANCE APPROACHES FOR SINGLE- FAMILY RESIDENTIAL BUILDINGSp.447

p.447SECTION 150.1 – PERFORMANCE AND PRESCRIPTIVE COMPLIANCE APPROACHES FOR SINGLE- FAMILY RESIDENTIAL BUILDINGSp.448

p.448SECTION 150.1 – PERFORMANCE AND PRESCRIPTIVE COMPLIANCE APPROACHES FOR SINGLE- FAMILY RESIDENTIAL BUILDINGS

p.449SECTION 150.1 – PERFORMANCE AND PRESCRIPTIVE COMPLIANCE APPROACHES FOR SINGLE- FAMILY RESIDENTIAL BUILDINGS