p.612TABLE 170.2-V – BESS Capacity Factors (Wh/ft2 of conditioned floor area)
| Building Type | CZ 1 | CZ 2 | CZ 3 | CZ 4 | CZ 5 | CZ 6 | CZ 7 | CZ 8 | CZ 9 | CZ 10 | CZ 11 | CZ 12 | CZ 13 | CZ 14 | CZ 15 | CZ 16 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Event & Exhibit | 1.82 | 1.95 | 1.74 | 2.12 | 1.91 | 2.13 | 2.24 | 2.30 | 2.36 | 2.47 | 2.62 | 2.16 | 2.64 | 2.68 | 3.22 | 1.89 |
| Library | 0.37 | 7.17 | 5.97 | 6.75 | 5.64 | 6.08 | 6.19 | 7.13 | 7.18 | 7.56 | 7.17 | 6.93 | 6.88 | 6.81 | 7.93 | 6.40 |
| Hotel/Motel | 0.86 | 0.84 | 0.77 | 0.92 | 0.81 | 0.89 | 0.90 | 1.01 | 1.00 | 1.11 | 1.14 | 0.96 | 1.18 | 1.18 | 1.49 | 0.85 |
| Office, Financial Institution, Unleased Tenant Space, Medical Office Building/Clinic | NR1 | 5.26 | 4.35 | 5.26 | 4.35 | 5.26 | 5.26 | 5.26 | 5.26 | 5.26 | 5.26 | 5.26 | 5.26 | 5.26 | 6.39 | 4.35 |
| Restaurant | 4.36 | 4.11 | 3.78 | 4.37 | 3.89 | 4.02 | 4.11 | 4.49 | 4.47 | 4.82 | 5.05 | 4.43 | 5.05 | 5.24 | 6.23 | 4.11 |
| Retail, Grocery | 1.89 | 1.82 | 1.71 | 1.82 | 1.72 | 1.80 | 1.76 | 1.92 | 1.97 | 2.05 | 2.22 | 1.95 | 2.16 | 2.29 | 2.66 | 1.91 |
| School | NR1 | 3.05 | 2.38 | 3.05 | 2.38 | 3.05 | 3.05 | 3.05 | 3.05 | 3.05 | 3.05 | 3.05 | 3.05 | 3.05 | 4.60 | 2.38 |
| Warehouse | NR1 | 0.41 | 0.37 | 0.41 | 0.37 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.54 | 0.37 |
| Religious Worship | 2.21 | 2.25 | 1.74 | 2.42 | 2.08 | 2.75 | 2.94 | 3.37 | 3.17 | 3.37 | 3.58 | 2.72 | 3.62 | 3.21 | 4.89 | 2.37 |
| Sports & Recreation | 1.26 | 0.98 | 0.76 | 1.14 | 0.86 | 1.20 | 1.23 | 1.57 | 1.53 | 1.65 | 1.83 | 1.27 | 1.86 | 1.57 | 3.02 | 1.13 |
| Multifamily > 3 stories | 1.88 | 2.27 | 1.88 | 2.27 | 1.88 | 2.27 | 2.27 | 2.27 | 2.27 | 2.27 | 2.27 | 2.27 | 2.27 | 2.27 | 2.85 | 1.88 |
p.610(h) Battery Energy Storage System (BESS) requirements—more than three habitable stories.
p.609Table 170.2-U – PV Capacity Factors (W/ft2 of conditioned floor area)
p.610All buildings that are required by Section 170.2(g) to have a PV system shall also have a BESS meeting the minimum qualification requirements of Reference Joint Appendix JA12. The rated energy capacity shall be not less than the Minimum Rated Useable Energy Capacity determined by Equation 170.2-E, or by Equation 170.2-F if SARA was used to determine the PV capacity in Section 170.2-D. and the rated power capacity shall be not less than the Minimum Power Capacity determined by Equation 170.2-G. In mixed occupancy buildings, the total battery system capacity for the building shall be determined by applying the Minimum Rated Usable Energy Capacity to each of the listed building types and summing the capacities determined for each.
| Building Type | CZ 1 | CZ 2 | CZ 3 | CZ 4 | CZ 5 | CZ 6 | CZ 7 | CZ 8 | CZ 9 | CZ 10 | CZ 11 | CZ 12 | CZ 13 | CZ 14 | CZ 15 | CZ 16 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Event & Exhibit | 3.48 | 4.28 | 3.66 | 4.32 | 3.77 | 4.05 | 4.28 | 4.83 | 4.63 | 4.80 | 5.04 | 4.44 | 4.95 | 4.36 | 5.48 | 3.38 |
| Library | 0.39 | 3.23 | 2.59 | 3.25 | 2.48 | 2.74 | 3.04 | 3.49 | 3.32 | 3.69 | 3.79 | 3.32 | 3.79 | 3.37 | 4.49 | 2.84 |
| Hotel/Motel | 1.69 | 1.90 | 1.66 | 1.97 | 1.69 | 1.87 | 1.94 | 2.22 | 2.09 | 2.20 | 2.30 | 2.05 | 2.30 | 2.02 | 2.72 | 1.73 |
| Office, Financial Institution, Unleased Tenant Space, Medical Office Building/Clinic | 2.59 | 3.13 | 2.59 | 3.13 | 2.59 | 3.13 | 3.13 | 3.13 | 3.13 | 3.13 | 3.13 | 3.13 | 3.13 | 3.13 | 3.80 | 2.59 |
| Restaurant | 8.55 | 9.32 | 8.16 | 9.65 | 8.21 | 8.73 | 9.11 | 10.18 | 9.75 | 10.28 | 10.85 | 9.73 | 10.69 | 9.73 | 12.25 | 8.47 |
| Retail, Grocery | 3.14 | 3.49 | 3.01 | 3.61 | 3.05 | 3.27 | 3.45 | 3.83 | 3.65 | 3.81 | 4.09 | 3.64 | 3.99 | 3.71 | 4.60 | 3.21 |
| School | 1.27 | 1.63 | 1.27 | 1.63 | 1.27 | 1.63 | 1.63 | 1.63 | 1.63 | 1.63 | 1.63 | 1.63 | 1.63 | 1.63 | 2.46 | 1.27 |
| Warehouse | 0.39 | 0.44 | 0.39 | 0.44 | 0.39 | 0.44 | 0.44 | 0.44 | 0.44 | 0.44 | 0.44 | 0.44 | 0.44 | 0.44 | 0.58 | 0.39 |
| Religious Worship | 4.25 | 4.65 | 3.49 | 4.52 | 3.72 | 4.29 | 4.64 | 5.89 | 5.30 | 5.67 | 5.89 | 4.99 | 5.78 | 4.63 | 7.57 | 3.90 |
| Sports & Recreation | 2.47 | 1.97 | 1.54 | 2.03 | 1.60 | 1.84 | 1.98 | 2.63 | 2.47 | 2.60 | 2.75 | 2.20 | 2.72 | 2.15 | 4.03 | 1.81 |
| Multifamily > 3 stories | 1.82 | 2.21 | 1.82 | 2.21 | 1.82 | 2.21 | 2.21 | 2.21 | 2.21 | 2.21 | 2.21 | 2.21 | 2.21 | 2.21 | 2.77 | 1.82 |
p.610EQUATION 170.2-E BATTERY ENERGY STORAGE SYSTEM MINIMUM RATED USABLE ENERGY CAPACITY
Equation text: kWhbatt = ((CFA x B)/(1000 x C0.5))
Needs visual review
p.610EQUATION 170.2-F - BATTERY ENERGY STORAGE SYSTEM MINIMUM RATED USABLE ENERGY CAPACITY, SARA-ADJUSTED
Equation text: kWhbatt = ((CFA x B)/(1000 x C0.5)) x (kWPVdc,SARA/kWPVdc)
Needs visual review
p.610kWhbatt = Minimum Rated Usable Energy Capacity of the BESS in kWh. kWPVdc = Minimum Rated PV System Capacity in kW from Equation 170.2-D kWPVdc, SARA = Minimum Rated PV System Capacity in kW from the SARA calculation.
p.612Footnote to TABLE 170.2-V:
p.6121. NR = Not Required
p.610CFA = Conditioned floor area that is subject to the PV system requirements of
p.610Section 170.2(g) in square feet.
p.610B = BESS Capacity Factor in Wh/square foot as specified in Table 170.2-V for
p.610the building type.
p.610C = Rated single charge-discharge cycle AC to AC (round-trip) efficiency of the
p.610BESS.
p.609SECTION 170.2 – PRESCRIPTIVE APPROACH
p.610EQUATION 170.2-G BATTERY ENERGY STORAGE SYSTEM MINIMUM RATED POWER CAPACITY
p.610kWbatt = kWhbatt / 4
p.610kWbatt = Minimum Rated Power Capacity of the BESS in kWdc
p.610kWhbatt = Minimum Rated Usable Energy Capacity of the BESS in kWh Exception 1 to Section 170.2(h): No BESS is required if the installed PV system capacity is less than 15 percent of the capacity determined by Equation 170.2-D.p.611