p.463a. New roofing products in Climate Zones 4 and 6 through 15 shall have an aged
p.467a. Bathroom local mechanical exhaust. Altered bathroom local mechanical
p.462with a communication interface that either meets the requirements of Section 110.12(a) or has an ANSI/CTA-2045-B communication port; or
p.464the manufacturer’s installation instructions as per California Residential Code Section R900; or
p.466and duct material, if the reused parts are accessible and can be sealed to prevent leakage.
p.468B. The standard design for an altered component shall be the higher efficiency of
p.4692. The standard design shall assume the same geometry and orientation as the proposed design.
p.463solar reflectance equal to or greater than 0.63 and a thermal emittance equal or greater than 0.75, or a minimum SRI of 75.
p.467exhaust systems shall comply with the applicable requirements specified in Section 150.0(o)1G.
p.468existing conditions or the requirements stated in Table 150.2-G. For components not being altered, the standard design shall be based on the existing conditions. When the third party verification option is specified as a requirement, all components proposed for alteration for which the additional credit is taken, must be verified by a certified ECC-Rater.
p.462c. A single heat pump water heater that meets the requirements of NEEA
p.464ii. Replaced roofing abuts sidewall or parapet walls and the addition of insulation required by Table 150.2-F would reduce the height from the roof surface to the top of the base flashing to less than that set forth in the manufacturer’s installation instructions as per the California Residential Code Section R900, provided that the following conditions apply:
p.466M. Mechanical ventilation for indoor air quality - altered ventilation systems. Altered
p.4693. The “existing efficiency level” modeling rules, including situations where nameplate data are not available, are described in Sections 10-109(c) and 10-116.
p.465iii. In Climate Zones 1 through 4 and 8 through 16, recessed downlight luminaires in the ceiling shall be covered with insulation to the same depth as the rest of the ceiling. Luminaires not rated for insulation contact must be replaced or retrofitted with a fireproof cover that allows for insulation to be installed directly over the cover; and
p.467b. Kitchen local mechanical Exhaust. If the kitchen local ventilation fan is
p.462Advanced Water Heater Specification Tier 3 or higher; or
p.466ventilation system components or newly installed ventilation equipment serving the alteration shall comply with Section 150.0(o) as applicable subject to the requirements specified in subsections i and ii below.
p.467altered or replaced, then one of the following subsections 1, 2, or 3 shall be used for compliance as applicable.
p.462d. If the existing water heater is an electric resistance water heater, a
p.462consumer electric water heater; or
p.466i. Whole-dwelling unit mechanical ventilation.
p.4671. Dwellings that were required by a previous building permit to comply with the kitchen local exhaust requirements in 150.0(o)1G shall meet or exceed the applicable airflow or capture efficiency requirements in Section 150.0(o)1G.
p.462e. A water-heating system determined by the Executive Director to use no
| Minimum Aged Solar Reflectance | Roof Deck Continuous Insulation R-value (Climate Zones 6-7) | Roof Deck Continuous Insulation R-value (Climate Zones 2, 4, & 8-15) |
|---|---|---|
| 0.60 | 2 | 16 |
| 0.55 | 4 | 18 |
| 0.50 | 6 | 20 |
| 0.45 | 8 | 22 |
| No Requirement | 10 | 24 |
| Altered Component | Standard Design Without Third Party Verification of Existing Conditions Shall be Based On | Standard Design With Third Party Verification of Existing Conditions Shall be Based On |
|---|---|---|
| Ceiling Insulation, Wall Insulation, and Raised-floor Insulation | The requirements of Sections 150.0(a), (c), and (d). | The existing insulation R-value. |
| Fenestration | The requirements of Section 150.1(c)3A. | The existing fenestration U-factor and SHGC values as verified. |
| Window Film | The requirements of Section 150.1(c)3A. | The existing fenestration in the alteration shall be based on Table 110.6-A and Table 110.6-B. |
| Doors | The U-factor of 0.20. The door area shall be the door area of the existing building. | If the proposed U-factor is < 0.20, the standard design shall be based on the existing U-factor value as verified. Otherwise, the standard design shall be based on the U-factor of 0.20. The door area shall be the door area of the existing building. |
| Space-Heating and Space- Cooling Equipment | TABLE 150.1-A for equipment efficiency requirements; Section 150.2(b)1C for entirely new or complete replacement systems; Section 150.2(b)1F for refrigerant charge verification requirements. | The existing efficiency levels. |
| Air Distribution System – Duct Sealing | The requirements of Sections 150.2(b)1D and 150.2(b)1E | The requirements of Sections 150.2(b)1D and 150.2(b)1E |
| Air Distribution System – Duct Insulation | The proposed efficiency levels. | The existing efficiency levels. |
| Water Heating Systems | The requirements of Section 150.2(b)1Hii | The existing efficiency level. |
| Roofing Products | The requirements of Section 150.2(b)1I. | The requirements of Section 150.2(b)1I |
| All Other Measures | The proposed efficiency levels. | The existing efficiency levels. |
p.462more energy than the one specified in Item a above; or if no natural gas is connected to the existing water heater location, a water-heating system determined by the executive director to use no more energy than the one specified in Item d above.
p.466a. Whole-dwelling unit airflow. If the whole-dwelling ventilation fan is altered
p.4641. The sidewall or parapet walls are finished with an exterior cladding material other than the roof covering membrane material; and
p.466or replaced, then one of the following subsections 1 or 2 shall be used for compliance as applicable.
p.469(c) Whole building. Any addition or alteration may comply with the requirements of Title 24,
p.4642. The sidewall or parapet walls have exterior cladding material that must be removed to install the new roof covering membrane to maintain the minimum base flashing height; and
p.4672. Dwellings that were required by a previous building permit to install a vented kitchen range hood or other kitchen exhaust fan, shall install a replacement fan that meets or exceeds the airflow required by the previous building permit, or 100 cfm, whichever is greater.
p.4661. Dwellings that were required by a previous building permit to comply with the whole-dwelling unit airflow requirements in Section 150.0(o) shall meet or exceed the whole-dwelling unit mechanical ventilation airflow specified in Section 150.0(o)1C, 150.0(o)1E or 150.0(o)1F as confirmed through field verification and diagnostic testing in accordance with the applicable procedures specified in Reference Residential Appendix RA3.7.
p.469Part 6 by meeting the requirements for the entire building.
p.465iv. Attic ventilation shall comply with the California Residential Code, Title 24, Part 2.5, Section R806.
p.462I. Roofs. Replacements of the exterior surface of existing roofs, including adding a new
p.462surface layer on top of the existing exterior surface, shall meet the requirements of Section 110.8 and the applicable requirements of Subsections i and ii where more than 50 percent of the roof is being replaced.
p.4643. The ratio of the replaced roof area to the linear dimension of affected sidewall or parapet walls is less than 25 square feet per linear foot; or
p.4673. Dwellings that were not required to have a kitchen local ventilation exhaust system according to the conditions in either subsection 1 or 2 above shall not be required to comply with the requirements of Section 150.0(o)1G.
p.462i. Steep-sloped roofs. Steep-sloped roofs shall meet the following:
p.462New roofing products in Climate Zones 4 and 8 through 15 shall have a minimum aged solar reflectance of 0.20 and a minimum thermal emittance of 0.75, or a minimum SRI of 16.
p.4662. Dwellings that were not required by a previous building permit to have a whole-dwelling unit ventilation system shall not be required to comply with the whole-dwelling unit ventilation airflow specified in Section 150.0(o)1C, 150.0(o)1E or 150.0(o)1F.
p.467c. Replacement Ventilation Fans. New or replacement local mechanical exhaust
p.467fans shall be rated for airflow and sound in accordance with the requirements of ASHRAE 62.2 Section 7.1 and Title 24, Part 6 Section 150.0(o)1Gvi. Additionally, when compliance with a specified exhaust airflow rate is required, the replacement fan shall be rated at no less than the airflow rate required for compliance.
p.466b. Replacement ventilation fans. Whole-dwelling unit replacement ventilation
p.463b. Roofs shall be insulated to the levels specified in Table 150.2-F.
p.462a. Buildings with ceiling assemblies with a U-factor lower than or equal to 0.025
p.466fans shall be rated for airflow and sound in accordance with the requirements of ASHRAE 62.2 Sections 7.1 and 7.3. Additionally, when conformance to a specified whole-dwelling unit airflow rate is required for compliance, the replacement fans shall be rated at no less than the airflow rate required for compliance.
p.468Space-Heating and Space-
p.462or that are insulated with at least R-38 ceiling insulation; or
p.468Cooling Equipment
p.467N. Exterior doors. Alterations that add exterior door area shall meet the U-factor
p.462b. Buildings with a radiant barrier in the attic, where the radiant barrier is not
| Climate Zone | Continuous Insulation R-value | Roof Assembly U-factor |
|---|---|---|
| 3, 5-7 | NR | NR |
| 1, 2, 4, 8-16 | R-14 | 0.039 |
p.467requirement of Section 150.1(c)5.
p.462installed directly above spaced sheathing, meeting the requirements of
p.4672. Performance approach.
p.465K. Lighting. The altered lighting system shall meet the lighting requirements of Section 150.0(k). The altered luminaires shall meet the luminaire efficacy requirements of Section 150.0(k). Where existing screw base sockets are present in ceiling-recessed luminaires, removal of these sockets is not required provided that new JA8 compliant trim kits or lamps designed for use with recessed downlights or luminaires are installed.
p.464J. Ceiling. Vented attics shall meet the following:
p.466c. Air filters. If the air filtration device for a whole-dwelling unit ventilation
p.462c. In Climate Zones 2, 4, 9, 10, 12 and 14, buildings that have no ducts in the
p.467The energy budget for alterations is expressed in terms of long-term system cost (LSC), and the altered component(s) and any newly installed equipment serving the alteration shall meet the applicable requirements of Subsections A, B, and C below.
p.466system is altered or replaced, then one of the following subsections 1 or 2 shall be used for compliance as applicable.
p.462attic; or
p.464i. In Climate Zones 1 through 4, 6, and 8 through 16, insulation shall be installed to achieve a weighted U-factor of 0.020 or insulation installed at the ceiling level shall result in an insulated thermal resistance of R-49 or greater for the insulation alone; and
p.462d. Buildings with R-2 or greater continuous insulation above or below the roof
p.4661. Dwellings that were required by a previous building permit to comply with the ventilation system air filtration requirements in Section 150.0(m)12 shall comply with the air filtration requirements in Section 150.0(m)12.
p.462deck.
p.467A. The altered components shall meet the applicable requirements of Sections 110.0
p.467through 110.9, Sections 150.0(a) through (l), Sections 150.0(m)1 through 150.0 (m)10, and Sections 150.0(p) through (q). Entirely new or complete replacement mechanical ventilation systems as these terms are used in Section 150.2(b)1L, shall comply with the requirements in Section 150.2(b)1L. Altered mechanical ventilation systems shall comply with the requirements of Section 150.2(b)1M. Entirely new or complete replacement space-conditioning systems, and entirely new or complete replacement duct systems, as these terms are used in Sections 150.2(b)1C and 150.2(b)1Diia, shall comply with the requirements of Sections 150.0(m)12 and 150.0(m)13.p.468
p.465L. Mechanical ventilation for indoor air quality - entirely new or complete
p.465replacement ventilation Systems. Entirely new or complete replacement ventilation systems shall comply with all applicable requirements in Section 150.0(o). An entirely new or complete replacement ventilation system includes a new ventilation fan component and an entirely new duct system. An entirely new or complete replacement duct system is constructed of at least 75 percent new duct material, and up to 25 percent may consist of reused parts from the dwelling unit's existing duct system, including but not limited to registers, grilles, boots, air filtration devicesp.466
p.4662. Dwellings that were not required by a previous building permit to comply with the ventilation system air filtration requirements in 150.0(m)12 shall not be required to comply with the air filtration requirements specified in Section 150.0(m)12.
p.464ii. In Climate Zones 2, 4, and 8 through 16 air seal all accessible areas of the ceiling plane between the attic and the conditioned space in accordance with Section 110.7; and
p.468C. The proposed design shall be based on the actual values of the altered components. Notes to Section 150.2(b)2: 1. If an existing component must be replaced with a new component, that component is considered an altered component for the purpose of determining the standard design altered component energy budget and must meet the requirements of Section 150.2(b)2B.p.469
p.463i. Mechanical equipment is located on the roof and will not be temporarily disconnected and lifted as part of the roof replacement and the addition of insulation required by Table 150.2-F would reduce the height from the roof surface to the top of the base flashing to less than that set forth inp.464
p.466ii. Local mechanical exhaust.p.467
p.462ii. Low-sloped roofs. Low-sloped roofs shall meet the following:p.463
p.462SECTION 150.2 – ENERGY EFFICIENCY STANDARDS FOR ADDITIONS AND ALTERATIONS TO EXISTING SINGLE-FAMILY RESIDENTIAL BUILDINGS
p.463SECTION 150.2 – ENERGY EFFICIENCY STANDARDS FOR ADDITIONS AND ALTERATIONS TO EXISTING SINGLE-FAMILY RESIDENTIAL BUILDINGS
p.464SECTION 150.2 – ENERGY EFFICIENCY STANDARDS FOR ADDITIONS AND ALTERATIONS TO EXISTING SINGLE-FAMILY RESIDENTIAL BUILDINGS
p.465SECTION 150.2 – ENERGY EFFICIENCY STANDARDS FOR ADDITIONS AND ALTERATIONS TO EXISTING SINGLE-FAMILY RESIDENTIAL BUILDINGS
p.466SECTION 150.2 – ENERGY EFFICIENCY STANDARDS FOR ADDITIONS AND ALTERATIONS TO EXISTING SINGLE-FAMILY RESIDENTIAL BUILDINGS
p.467SECTION 150.2 – ENERGY EFFICIENCY STANDARDS FOR ADDITIONS AND ALTERATIONS TO EXISTING SINGLE-FAMILY RESIDENTIAL BUILDINGS
p.468SECTION 150.2 – ENERGY EFFICIENCY STANDARDS FOR ADDITIONS AND ALTERATIONS TO EXISTING SINGLE-FAMILY RESIDENTIAL BUILDINGS
p.469SECTION 150.2 – ENERGY EFFICIENCY STANDARDS FOR ADDITIONS AND ALTERATIONS TO EXISTING SINGLE-FAMILY RESIDENTIAL BUILDINGS