

Text in this table
2025 Building Energy Efficiency Standards SECTION 180.2 – ALTERATIONS d. Air filters. If the air filtration device for a whole-dwelling unit ventilation system is altered or replaced, then one of the following Subsections 1 or 2 shall be used for compliance. 1. Dwellings that were required by a previous building permit to comply with the ventilation system air filtration requirements in Section 160.2(b)1, 120.1(b)1 or 150.0(m)12 shall comply with the air filtration requirements in Section 160.2(b)1. 2. Dwellings that were not required by a previous building permit to comply with the ventilation system air filtration requirements in Section 160.2(b)1, 120.1(b)1 or 150.0(m)12 shall not be required to comply with the air filtration requirements specified in Section 160.2(b)1. ii. Local mechanical exhaust. a. Bathroom local mechanical exhaust. Altered bathroom local mechanical exhaust systems shall comply with the applicable requirements specified in Section 160.0(b)2Avi. b. Kitchen local mechanical exhaust. If the kitchen local ventilation fan is altered or replaced, then one of the following Subsections 1, 2 or 3 shall be used for compliance. 1. Dwellings that were required by a previous building permit to comply with the kitchen local exhaust requirements in Section 160.0(b)2Avi, 120.1(b)2vi or 150.0(o)1G shall meet or exceed the applicable airflow or capture efficiency requirements in Section 160.0(b)2Avi. 2. Dwellings that were required by a previous building permit to install a vented kitchen range hood or other kitchen exhaust fan shall install a replacement fan that meets or exceeds the airflow required by the previous building permit, or 100 cfm, whichever is greater. 3. Dwellings that were not required to have a kitchen local ventilation exhaust system according to the conditions in either Subsection 1 or 2 above shall not be required to comply with the requirements of Section 160.0(b)2Avi. c. Replacement ventilation fans. New or replacement local mechanical exhaust fans shall be rated for airflow and sound in accordance with the requirements of ASHRAE 62.2 Section 7.1 and Title 24, Part 6, Section 160.0(b)2Avif. Additionally, when compliance with a specified exhaust airflow rate is required, the replacement fan shall be rated at no less than the airflow rate required for compliance. (c) Performance approach. The altered component(s) and any newly installed equipment serving the alteration shall meet the applicable requirements of Subsections 1, 2 and 3 below. The energy budget for alterations is expressed in terms of Long-Term System Cost (LSC) energy.
| Control Specifications | Projects complying with Section 180.2(b)4Biva | Projects complying with Sections 180.2(b)4Bivb or 180.2(b)4Bivc |
|---|---|---|
| Manual Area Controls 160.5(b)4Ai | Required | Required |
| Manual Area Controls 160.5(b)4Aii | Required | Required |
| Manual Area Controls 160.5(b)4Aiii | Only required for new or completely replaced circuits | Only required for new or completely replaced circuits |
| Multilevel Controls 160.5(b)4B | Required | Not Required |
| Automatic Shut Off Controls 160.5(b)4Ci | Required | Required |
| Automatic Shut Off Controls 160.5(b)4Cii | Required | Required |
| Automatic Shut Off Controls 160.5(b)4Ciii | Required | Required |
| Automatic Shut Off Controls 160.5(b)4Civ | Required | Required |
| Automatic Shut Off Controls 160.5(b)4Cv | Required | Required |
| Automatic Shut Off Controls 160.5(b)4Cvi | Required | Required; except for 160.5(b)4Cvib |
| Daylight Responsive Controls 160.5(b)4D | Required | Not Required |
| Demand Responsive Controls 110.12(a) and 110.12(b) | Required | Not Required |